Part No. 4801-3030 Rev. 1-15
Page
13
of
22
Super Saver XL-240 Heater
9.2
1016 Direct Spark Ignition
Status Indicator Error Conditions
The status indicator LED will not be lit with power applied to the board and the control operating
properly. However, if the control is not operating properly, the status indicator LED will flash in
one of the following error codes.
1. Status Indicator Flashing One Time
When the status indicator LED shows the error code of a single repeated flash, the control is
in lock-out, because the sail switch was stuck closed.
2. Status Indicator Flashing Two Times
When the status indicator LED shows the repeating error code of two flashes, the control is in
lock-
out because the control circuits did not receive the “closed” signal from the high limit
switch, the sail switch, and the low gas pressure switch
*
within the required amount of time.
*ONLY HEATERS FOR USE WITH LP/PROPANE GAS ARE EQUIPPED WITH A LOW
GAS PRESSURE SWITCH.
3. Status Indicator Flashing Three Times
When the status indicator LED shows the repeating error code of three flashes, the control is
in lock-out due to either a failed ignition attempt, a gas valve error, or a false flame sensed
during the pre-purge of warm-up periods. If false flame has been sensed, the control will
return to normal operation, and begin a new ignition sequence when the false flame is no
longer present.
4. Status Indicator Flashing Four Times
When the status indicator LED shows the repeating error code of four flashes, the gas valve
is energized during no call for heat.
9.3
Checking Manifold Pressure
To be performed by a certified gas technician only!
1.
Unplug heater from power source and turn ball valve to OFF position.
2.
Remove outlet pressure tap plug from gas control valve and connect pressure gauge.
3.
Return electrical power to heater and plug to power source and turn ball valve to ON
position.
4.
To obtain an accurate manifold pressure reading, heater must be cycled on and off
several times to stabilize the pressure regulator diaphragm.
5.
Return the heater to operation and read pressure gauge.
6.
If necessary, adjust pressure regulator on gas control valve to the acceptable manifold
pressure found on rating plate and page 1
of owner’s manual.
7.
Remove pressure regulator adjustment screw.
8.
Using a screwdriver, turn inner adjustment screw clockwise to increase or counter
clockwise to decrease manifold pressure to burner.
9.
Always replace cap screw and tighten firmly to prevent gas leakage.
10.
Unplug heater from power source and turn ball valve to OFF position.
11.
Remove pressure gauge and replace outlet pressure tap plug.
12.
Return heater to operation and observe through at least one complete cycle to ensure all
controls are operating properly.
13.
Perform gas leak test at outlet pressure tap plug. (Soap and water work well).