14
4801-1020
Super-Saver XL
TM
Heater
3. Installation
Hanging the Heater
Chain Suspension
Mount the heater with chain hooks and chains so that the back of the heater is at least 12" (305 mm) from
the ceiling and wall. The heater must be a minimum of 20" (500 mm) from floor, and located so that
livestock and combustible materials are unable to come in contact with heater or within 10' (3 meters) of
the hot air discharge.
Cable Suspension
If frequent height adjustment is required, use cables and pulleys. Main line cable would be connected to
a winch.
Directions for Leveling
Adjust cables or chains as required to level the heater. Use a carpenter’s level to check that the heater
is level.
Installing the Dual-Flare Duct
Fold Dual-Flare duct (1) to shape as shown in
. Install Dual-Flare duct to heater exhaust as
shown with sheet metal screws (3) provided. This provides a multi-directional heat flow (2) that may be set
by bending flaps.
Figure 3A
Connecting the Gas Supply
For gas connection, attach the regulator (2) to the High Pressure Line (3) at the outside of the building as
shown in
. Connect flexible hose (1) to low pressure end of the regulator with special brass
coupling. Refer to table
for LP and natural gas requirements.
Figure 3B
1
3
2
Ref #
Description
1
Flare Duct
2
Adjust flap to direct heat flow.
3
Attach flare duct to heater with sheet
metal screws.
2
3
1
Ref #
Description
1
Flexible Hose
2
Gas Regulator
3
High Pressure Line