2. General Information
4801-1020
Super-Saver XL
TM
Heater
13
Heater Dimensions
Tools Required
1. Adjustable Wrench
2. Pipe Glue
3. Gas Leak Testing Solution
4. 1/4" (7 mm) Nut Driver
NOTE
:
Install screw hooks with hammer or drill.
Be Sure to Check Delivery
Locate packing slip and make sure all of the listed parts are enclosed. If not, call your Distributor
immediately.
Minimum Clearances
The heater must be located a minimum of 12" (305 mm) from the ceiling, a minimum of 12" (305 mm) from
the wall on the sides and back, a minimum of 20" (508 mm) from the ground, and positioned such that
livestock and combustible materials are unable to come in contact with the heater or within 10' (3 m) of the
hot air discharge.
Specifications and Requirements
NOTE
:
Refer to heater ratings plate for unit voltage, amperage, and frequency ratings.
Models
250K BTU Universal Mount
Weight
153 lbs.
Height
32" (81 cm)
Width
27-1/2" (70 cm)
Depth
19-1/4" (49 cm)
Model #
Maximum Input
Ventliation
(Air required to support combustion)
HH-SS-250-XL
250,000 BTUH (73.3 kW)
1200 CFM (2039 m
3
/hr)
LP/Propane
Gas
Maximum 14" W.C. (34.8 mbar) and minimum 12-1/2" W.C. (31.1 mbar) inlet gas supply pressure
acceptable at gas regulator connection. Burner manifold pressure 10" W.C. (24.9 mbar) at maximum
input. Gas pressure should be checked by a certified gas technician while heater is in operation.
Natural
Gas
Maximum 14" W.C. (34.8 mbar) and minimum 6" W.C. (14.9 mbar) inlet gas supply pressure
acceptable at gas regulator connection. Burner manifold pressure of 4" W.C. (9.9 mbar) at maximum
input. Gas pressure should be checked by a certified gas technician while heater is in operation.