background image

7

GG-NH3

Operation

Start-Up

Sensor can be response tested and/or span calibrated 

immediately after power up. Allow 60 seconds for 

power up time delay of sensor to end (green power 

LED will flash during power up).

Start-Up test:

  1) One person exposes each sensor to calibration gas.

  2) The second person stays at the control panel to 

determine that each sensor, when exposed to the 

gas, is connected to the proper input and responds, 

causing appropriate alarm functions.

LED Functions 

(see 

Figure 2

 on page 8)

Calibration

The GG-NH3 sensor comes factory calibrated and 

should require only minimal adjustment after 

installation. There are two pots on the preamp that 

are used for calibration (see 

Figure 2

).

Note:

 Never measure sensor output in mA. Always 

use mVDC or VDC voltmeter settings.

Zero Calibration:

 After the sensor is installed and has 

been powered up for a minimum of 8 hours, the unit 

can be zero calibrated by the following:

•  Be sure the unit is in clean air.
•  Adjust the zero pot until the sensor outputs 40 mV 

from Test [-] to Test [+] (see 

Figure 2

).

Note:

 To 

zero the sensor immediately after power up or cell 

replacement, unplug cell from the transmitter and 

adjust signal to 40 mV.

Span Calibration

: DO NOT ADJUST THE SPAN POT 

WITHOUT CERTIFIED CALIBRATION GAS! If span 

adjustment is required, use the following procedure:
• 

To enter calibration mode (disables all filtering and 

averaging), turn the Zero pot clockwise 1/4 turn and 

then back again. Successful entry into calibration 

mode will be indicated by the Power (green) LED 

blinking twice per second. Calibration mode will 

time out automatically after 4 minutes.

•  Apply span gas at 0.5 to 0.8 L/min (span gas must 

be in air, not nitrogen or other carrier).

•  Sensor should react to gas within 15 seconds.
•  Once the output signal has peaked (or 2 minutes 

maximum) adjust the Span pot until the correct 

output is achieved (see Figure 2). With full-scale 

span gas, the calculated span value is 200 mV. 

((span gas / sensor range * 16 + 4) (

mA output)

)

Note: Below are a few response characteristics which 

may be an indication that the gas sensor is at or near 

the end of its useful life. If any of these characteristics 

are observed, the cell should be replaced.
•  Slow response to / recovery from calibration gas.
•  Failure of the output to reach 50% of the calibration 

gas value prior to span adjustment.

•  Unable to achieve correct output during span.
•  Output at 0.5 mA due to SafeCell test failure.

Summary of Contents for GG-NH3

Page 1: ...Installation and Operation Manual GG NH3 AMMONIA GAS SENSOR...

Page 2: ...ly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Page 3: ...ting the Sensor 4 Installation Guidelines 5 Wiring 6 Operation 7 Start Up 7 Calibration 7 Maintenance 9 Specifications 10 Warranty 11 For technical support contact CTI 920 N Tradewinds Pkwy Columbia M...

Page 4: ...20 mA signal output will drop to 0 5 mA and the fault LED stays on solid This signal should be interpreted as a sensor fault at the control panel and prompt notification to plant personnel to investi...

Page 5: ...wire runs away from mercury vapor lights variable speed drives and radio repeaters to prevent electrical interference Protect sensor from physical damage forklifts etc Mounting screws should be screw...

Page 6: ...ded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all splice connections should be soldered Ground th...

Page 7: ...replacement unplug cell from the transmitter and adjust signal to 40 mV Span Calibration DO NOT ADJUST THE SPAN POT WITHOUT CERTIFIED CALIBRATION GAS If span adjustment is required use the following...

Page 8: ...ls On steady if supply voltage is less than 10VDC or SafeCell test fails for six hours Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks onc...

Page 9: ...term exposure to ammonia When the SafeCell test fails the fault red LED will blink once per second After six hours of continued and consecutive test failures the 4 20 mA signal output will drop to 0...

Page 10: ...inks once per second for 60 seconds during power up If supply voltage is too low 10 VDC or improperly grounded green LED will blink once per second continuously Stays steady on to indicate power Blink...

Page 11: ...air of the product by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a pr...

Page 12: ...ctiengineering com 866 394 5861 GG NH3 DOC1 3 20190605...

Reviews: