Installation Guidelines:

•  Remove and discard protective cell label.
•  Always mount sensor vertically.
•  Locate sensor to be easily accessible for calibration 

and maintenance.

•  Mount sensor close to potential leak source.
• 

Mount sensor in "breathing zone" (4'-5' above floor) 

for optimum personnel protection.

•  Take air movement and ventilation patterns into 

account.

•  Keep sensor and wire runs away from mercury 

vapor lights, variable speed drives, and radio 

repeaters to prevent electrical interference.

•  Protect sensor from physical damage (forklifts, etc).
•  Mounting screws should be screwed into studs 

when mounting on a wall with studs.

•  Never mount the sensor in CA (controlled 

atmosphere) rooms. Normal atmospheric levels of 

oxygen are required for operation.

•  More than one sensor should be installed in each 

room for highly critical locations.

•  Mount sensor enclosure through the mounting 

holes as shown in 

Figure 1

.

2.0"

6.5"

6.8"

7.75"

Figure 1: Mounting Dimensions

Summary of Contents for GG-NH3

Page 1: ...Installation and Operation Manual GG NH3 AMMONIA GAS SENSOR...

Page 2: ...ly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Page 3: ...ting the Sensor 4 Installation Guidelines 5 Wiring 6 Operation 7 Start Up 7 Calibration 7 Maintenance 9 Specifications 10 Warranty 11 For technical support contact CTI 920 N Tradewinds Pkwy Columbia M...

Page 4: ...20 mA signal output will drop to 0 5 mA and the fault LED stays on solid This signal should be interpreted as a sensor fault at the control panel and prompt notification to plant personnel to investi...

Page 5: ...wire runs away from mercury vapor lights variable speed drives and radio repeaters to prevent electrical interference Protect sensor from physical damage forklifts etc Mounting screws should be screw...

Page 6: ...ded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all splice connections should be soldered Ground th...

Page 7: ...replacement unplug cell from the transmitter and adjust signal to 40 mV Span Calibration DO NOT ADJUST THE SPAN POT WITHOUT CERTIFIED CALIBRATION GAS If span adjustment is required use the following...

Page 8: ...ls On steady if supply voltage is less than 10VDC or SafeCell test fails for six hours Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks onc...

Page 9: ...term exposure to ammonia When the SafeCell test fails the fault red LED will blink once per second After six hours of continued and consecutive test failures the 4 20 mA signal output will drop to 0...

Page 10: ...inks once per second for 60 seconds during power up If supply voltage is too low 10 VDC or improperly grounded green LED will blink once per second continuously Stays steady on to indicate power Blink...

Page 11: ...air of the product by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a pr...

Page 12: ...ctiengineering com 866 394 5861 GG NH3 DOC1 3 20190605...

Reviews: