C T I 2552 Installation and O peration G uide
Figure 2
Word Input to the PLC from the Module
1.3 Digital Word Map
RTD and/or millivolt signals are translated into a 14-bit digital word. Since the PLC requires a 16-bit
input word, the 14-bit value from the converter is placed into a 16-bit word for transmittal to the PLC.
As shown in the following figure, of the two bits not used for the digital word, one is used to show the
sign of the word, while the other is used to note values which are "overrange."
1.4 RTD Input to Digital Conversion
The following equations may be used to calculate the digital word in decimal format which will result
from a particular RTD input:
RTD Mode, Digital Word (WX) =
Degrees X 10
Millivolt Mode, Digital Word (WX) =
Millivolts X 100
As an example, the following figure illustrates the effects of a change in input level going from 0
degrees to 102.4 degrees in the RTD Input Mode.
Summary of Contents for 062-00108
Page 4: ...iv CTI 2552 Installation and Operation Guide ...
Page 6: ...vi CTI 2552 Installation and Operation Guide ...
Page 8: ...viii CTI 2552 Installation and Operation Guide ...
Page 10: ...x CTI 2552 Installation and Operation Guide ...
Page 13: ...CTI 2552 Installation and Operation Guide 3 Figure 3 Example Change Input Level ...
Page 16: ...6 CTI 2552 Installation and Operation Guide ...
Page 24: ...14 CTI 2552 Installation and Operation Guide CAUTION RTD wires must be of the same gauge ...
Page 28: ...18 CTI 2552 Installation and Operation Guide ...
Page 30: ...20 CTI 2552 Installation and Operation Guide ...
Page 34: ...24 CTI 2552 Installation and Operation Guide USER NOTES ...
Page 36: ...26 CTI 2552 Installation and Operation Guide ...