Start-up
RG1-Nb
RG1-Fb
Adjusting gas burner and boiler
The burner can be put into operation once the installation and assembly work has been completed.
•
Measure inlet pressure with U-pipe pressure gauge at measuring point "A".
max. 360 mbar (KE 15), max. 70 mbar (KE 10, static pressure)
min. 18 mbar (flow pressure) on RG1...-N
min. 35 mbar (flow pressure) on RG1-F
•
Burner and gas assembly are preset at factory to low output. This enables a soft burner start-up.
•
Adjusting the burner to the desired nominal output in accordance with the adjustment tables on
Pages 10, 11.
To do so:
•
Check gas working pressure with U-pipe pressure gauge at measuring point "B" outlet pressure.
Caution !
Minimum pressure difference (inlet-outlet pressure) 5 mbar!
•
Adjust gas pressure and air flow measurement "A" according to adjustment tables, PP. 10, 11.
•
Check exhaust gas values here without fail (CO, CO
2
or O
2
).
•
Depending on the system, the setting values must be corrected.
•
After completion of adjustment, check the setting data.
•
Check the gas pressure monitor after start-up. To do so, close ball valve slowly; burner must shut
down but not go into fault mode.
Burner output
Boiler output
at
η
= 92%
Gas type
Natural gas LL: H
i,n
= 9.3
[
kWh/m
3
]
Air flow
measurement "A"
[
kW
]
[
kW
]
Gas nozzle pressure
[
mbar
]
Gas flow
[
m
3
/h
]
[
mm
]
25.0
23
LL
2.1
2.9
10 - 11
33.7
31
LL
3.8
3.9
11 - 12
39.1
36
LL
5.5
4.5
12 - 13
44.6
41
LL
6.8
5.1
13 - 15
50.0
46
LL
8.7
5.7
15 - 18
58.7
54
LL
11.7
6.7
20 - 26
Burner output
Boiler output
at
η
= 92%
LPG 3B/P: H
i,n
= 25.8
[
kWh/m
3
]
Air flow
measurement "A"
[
kW
]
[
kW
]
Gas nozzle pressure
[
mbar
]
Gas flow
[
m
3
/h
]
[
mm
]
25
23
2.8
1.0
10 - 11
33.7
31
5.3
1.4
11 -12
39.1
36
7.2
1.6
12 - 13
44.6
41
9.0
1.8
13 - 15
50.0
46
11.0
2.1
15 - 18
58.7
54
14.0
2.4
20 - 26
Exhaust gas values
Natural gas LL+E
LPG propane 3B/P
O
2
content
3.5-5.0%
CO
2
content
9-10%
11-12%