95
CTC EcoZenith i350
Example in which “Heating mode” is normally “On” in the
heating season, but when terminal block K24 is closed, “Off”
is activated and the heating is switched off.
Activate/select function.
When an input is assigned, the function must
be activated or set in the Settings menu.
In the example with remote controlled “Heating,
ext. mode”, K24 is assigned. A selection is
then made of what is normal mode (arrow 1).
Here, the normal mode has been selected as:
Heating, mode (On)
When this has been done, you programme
what is to happen at Remote Control/
Heating, external mode HS1 (closed input,
arrow 2).
Arrow 2 indicates the selection "Off".
In this example the heating is always on. (Normal mode)
However, when terminal block K24 is closed, “Off” is
activated and the heating is switched off. The heating
remains switched off until you choose to start heating
up by opening K24.
The functions in remote control.
HP tariff
When electricity suppliers use a differentiated tariff, you
have the opportunity to block the heat pump when the
electricity tariff is high.
Tariff el.
When electricity suppliers use a differentiated tariff, you
have the opportunity to block the immersion heater
when the electricity tariff is high.
Night reduction
Night reduction means that you reduce the temperature
indoors during scheduled periods, for example at night
or when you are at work.
Ripple control
Disconnecting the compressor and immersion heater
during a certain period which is defined by the electricity
supplier (special equipment).
Ripple control is a device which an electricity supplier
can fit with the aim of disconnecting high current draw
equipment for a short period of time. The compressor
and electrical power are blocked when ripple control is
active.
Additional Domestic Hot Water
You select this option if you want to activate the Extra
DHW function.
Open terminal block = "On" (in this example)
Closed terminal block = “Off” (in this example)
K24
K24
Heating circuit
Max primary flow ºC
60
Min primary flow ºC
Off
Heating, mode
Auto
Heating, mode, ext
Heating off, out ºC
18
Heating off, time
120
Inclination ºC
50
Adjustment ºC
0
Night reduction disable ºC
-14
Room temp reduced ºC
-2
or
Primary flow reduced ºC
-3
Alarm room temp ºC
5
Smart low price ºC
1
Smart over capacity ºC
2
Max time heating
20
Charge pump %
60
Drying period mode
Off
Drying period temp ºC
25
1
2
On
i
NB: If both the heat pump and the
immersion heater are blocked, the
building may be without heating
for a long time. It is therefore
recommended that you only block
the immersion heater with the tariff.
Summary of Contents for EcoZenith i350 H
Page 4: ...4 CTC EcoZenith i350...
Page 27: ...27 CTC EcoZenith i350...
Page 29: ...29 CTC EcoZenith i350...
Page 30: ...30 CTC EcoZenith i350 X2 6 4 Wiring diagram CTC EcoZenith i350 3x400V...
Page 32: ...32 CTC EcoZenith i350 X2 6 5 Wiring diagram CTC EcoZenith i350 1x230V...
Page 34: ...34 CTC EcoZenith i350 X2 6 6 Wiring diagram CTC EcoZenith i350 3x230V...
Page 105: ...105 CTC EcoZenith i350...
Page 115: ......