69
CTC EcoLogic M/L
Solar test tank min
4 (1...20)
(Used only if evacuated tube solar collectors have been
defined.) When recharging the bedrock, switching to
tank charging is done once every 30 minutes to check
whether tank charging is possible. The test is carried
out at the set time interval. If enough temperature
is obtained, tank charging continues; otherwise the
system switches to charging the bedrock again.
Test frequency min
30 (0...180)
Specifies the frequency at which the Solar Test function
should perform. With 0 as the set value, solar test takes
place continuously.
Winter mode
Off (Off/On)
Deactivate the "Solar test tank min" function. "Off"
means only borehole charging.
Flow l/mln
6.0 (0.1...50.0)
The flow circulating through the solar panels should be
indicated here. (This can be read from the flow meter in
the system unit.) The flow should be read when pump
G30 is running at 100%.
NB:
It is important the value is correct, as the flow
is used as the basis for calculating the power and
cumulative energy. Incorrect flows will therefore produce
incorrect values for these parameters.
Protection collector
Refer to the "Settings Protection Collector" chapter
below.