Vecto
III
User Manual
17
•
4 GB on-board storage providing data storage of all IEC 61000-4-30
voltage and current 10-minute values up to the 63
rd
harmonic
component.
•
Time stamping
•
GPS time synchronization resulting in a time-stamping certainty better
than 1 µs.
•
PTP time synchronization resulting in a time-stamping certainty better
than 100 µs.
•
NTP time synchronization as an option.
•
Communication
•
Communication is via Ethernet.
•
Modbus over Ethernet.
•
DNP3 over Ethernet.
•
IEC 61850
–
optional.
•
Advanced triggering
•
User-configurable triggering between different devices: the patented
Xross-Trigger feature (Described in the Osprey Lite user manual)
•
Configuration of device
•
The Vecto III has to be configured by means of an Ethernet connection to a
local laptop with Osprey Lite installed.
•
Data analysis and reporting
•
Osprey Lite is supplied free of charge and continuously updated.
•
Download from www.ctlab.com.
•
It generates both NRS 048 and EN 50160 PQ reports.
•
It allows basic and advanced analysis of PQ waveform events and
trends.
•
Data can be exported to in .csv and PQDIF format for additional analysis
in third party software packages.
•
Data downloading can be automated by configuration of the Vecto III
with Osprey Lite.
Summary of Contents for Vecto III
Page 63: ...Vecto III User Manual 63 Figure 33 CT circuit connection layout...
Page 70: ...Vecto III User Manual 70 Appendices 1 Vecto III dimensions...
Page 71: ...Vecto III User Manual 71 2 Vecto III wiring diagram...
Page 72: ...Vecto III User Manual 72 3 Vecto III Top View...
Page 74: ...Vecto III User Manual 74 2964 2197 2569 3541...
Page 76: ...Vecto III User Manual 76 2964 2197 2569 3541 1084...
Page 78: ...Vecto III User Manual 78 2934 1084 3539 2431 2951 2487 2964 2535 2486 2571 2488 2344 2346 2600...