SIGNATURE 2
Master Programming Mode
11
Master Programming Mode
To enter Master Programming Mode, press and hold both buttons for 5 seconds.
Note: All Master Programming functions have been preset at the factory. Unless a change is desired, it is
NOT
necessary to enter Master Programming Mode.
1.
Regeneration
Time
(r)
Example (
r 12A
)
-The time of day at which regeneration may take place is designated by the letter “
r
”.
-Default regeneration time setting is
12A
-The first display digit indicates A.M. or P. M. To change the value, press the
Set/Change
button.
-Press
Menu/Enter
button to accept the value and move to the next digit.
-The second and third display digits indicate the hour at which the regeneration will occur.
-Change the digits with the
Set/Change
button and accept with the
Menu/Enter
button.
-After the entire display flashes, press the
Menu/Enter
button to move to the next menu item.
2.
Backwash Cycle Step Times* (Steps 5, 6, 7, 8)
Example (
3 - 20
)
- The next 4 displays set the duration of time in minutes for each backwash cycle step.
- The step number which is currently modifiable is indicated on the far left of the display screen.
- The number of minutes allotted for the selected backwash step is displayed on the far right.
- Change the digit values using the
Set/Change
and
Menu/Enter
buttons as described above.
Note on Air Draw Cycle (7):
The longer the unit is set to remain in the Air Draw cycle (7), the more air is drawn into the system.
A default setting of 20 minutes draws air down to the level of a normal media bed height. If the
system needs more air, increase the time setting for step (7) or decrease the number of days
between air draw cycles.
3.
Bluetooth Enabled
BE - 1
(ON)
BE - 0
(OFF)
4.
Bluetooth Password
BBPP
is displayed for one second, then password is displayed.
5. To Exit the Master Programming Mode, press the
Menu/Enter
button until time of day returns.
Note
: If no buttons are pressed for 60 seconds, the Master Programming Mode will be exited
automatically.