MINIMUM DISTANCES FOR THE POSITIONING OF THE AIR INTAKE
For correct and safe positioning of the air intake (see
fig.9) where the minimum distances for any opening are
indicated. It is important to consider possible wall outlets
from other machines or kitchen aspiration hoods.
10. ELECTRICAL CONNECTIONS
All machines are equipped with power cables, for which, in case of the need for replacing, an authorised
technician must be used.
Before connecting to the power supply, check that:
•
the electric plant has been fitted with a 6A magnetothermal switch
•
the characteristics of the plant are sufficient enough to satisfy what is indicated on the machine
characteristic plaque (electric power, nominal voltage etc...)
•
that the plant has a sufficient earth connection according to nominal regulations in vigour (earth connection
is obligatory by law)
•
the power cable should never. at any point, overheat 50°C above room temperature: If a direct connect ion is
desired, it is necessary to use an omnipolar switch, with a minimum opening between contacts of 3mm, that
has been designed for the electrical charge indicated on the plaque and must correspond to regulations in
vigour. the earth wire, brown/green, should not be interrupted by the switch. The plug or omnipolar switch
must be readily accessible once the machine has been installed
Disconnect the power supply when not using the machine for a prolonged period of time.
The manufacturer declines all responsibility if the above indicated anti-injury regulations are not
respected.
Fig. 9
AIR INTAKE