46
Does
spark stop
when pilot
lights?
24 volts
across
terminals
2
&
3
at S8670?
Spark
across
ignitor/sensor
gap?
Y
Can you
hear
sparking?
*
Defective
S8670
module
*
Break in
spark cable
insulation
*
Break in pilot
porcelain
*
Incorrect
pilot spark gap
*
Loose
connection in
spark cable
*
Loose
ground
connection
N
Pilot
lights?
Y
N
N
*
Defective
S8670 module
24 volts
across
PV
&
MV/PV
at gas
valve?
*
Defective EI
wiring
harness.
N
*
Loose connection
in ignition cable or
ground wire
*
Pilot electrode
porcelain cracked
*
Pilot flame not
covering gap
between electrode
and grounding
strap
*
Low gas pressure
at gas valve inlet
*
Defective S8670
module
Main
burner
lights?
N
Y
24VAC
across
terminals
1
&
2
on S8670?
Y
N
N
*
Defective
S8670
module
24 volts
between
MV
&
MV/PV
on gas
valve?
*
Defective
gas valve
*
Defective EI
harness
END
START
(24 volts is present across
5
and
6
on S8670, 30-50
second prepurge period has passed, but main
burners do not light)
N
Y
Y
N
Y
Y
Y
*
Low line pressure
*
Plugged, kinked or leaking
pilot tubing
*
Plugged pilot orifice
*
Gas line not purged of air
*
Defective pilot assembly
*
Defective gas valve
Intermittent Ignition System Troubleshooting Chart