XIII. Troubleshooting
A. Troubleshooting problems where no error code is displayed:
CONDITION
POSSIBLE CAUSES
Display Blank, Fan off, LWCO lights off
• No 120VAC Power at boiler. Check breaker and wiring
between breaker panel and boiler
Display Panel Blank, Fan running
• Loose 120VAC connection wiring between boiler J-Box and
MCBA
• Blown “F1” fuse in MCBA (see Figure 13.2 for location).
Replace with 5A fuse provided
Display reads “U.125” continuously, Fan running
• Defective AT250 transformer
• Blown “F3” fuse in MCBA (see Figure 13.2 for location).
Replace with 4A slow-blow fuse provided
Boiler not responding to call for heat, Status code on display
=”0” (see Figure 11.1)
• Boiler is not seeing call for heat. Check thermostat or
zone wiring for loose connection, miswiring, or defective
thermostat/zone control.
Boiler fires, but display panel is blank
• Loose ribbon cable
• Defective display
WARNING
TURN OFF POWER TO BOILER BEFORE REPLACING FUSES OR WORKING ON WIRING.
Table 13.1: No Error Code Displayed
Figure 13.2: MBCA Fuse Location
Summary of Contents for BIMINI BWC225
Page 2: ......
Page 22: ...20 PAGE INTENTIONALLY LEFT BLANK ...
Page 23: ...21 PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...22 PAGE INTENTIONALLY LEFT BLANK ...
Page 29: ...Figure 8 3 Piping Method 1 Heat Indirect Water Heater 27 ...
Page 37: ...Figure 9 1 Wiring Connections Diagram 35 ...
Page 38: ...Figure 9 2 Ladder Diagram 36 ...
Page 39: ...Figure 9 3 Wiring of Isolation Relay for Control of Two Heating Circulators 37 ...
Page 56: ...54 PAGE INTENTIONALLY LEFT BLANK ...
Page 60: ...58 ...
Page 61: ...59 ...
Page 62: ...60 ...
Page 63: ...61 Gas Train Assembly Honeywell Valve ...
Page 64: ...Gas Train Assembly Dungs Valve 62 ...
Page 66: ...64 ...
Page 68: ...66 ...
Page 69: ...67 ...
Page 70: ...68 ...
Page 72: ......