12
TABLE 6.2b: SUMMARY OF VERTICAL VENTING OPTIONS
VENT OPTION #
6
7
CLASSIFICATION USED IN THIS
MANUAL
VERTICAL
DIRECT VENT
VERTICAL
DIRECT VENT
ILLUSTRATED IN FIGURE
6.4
6.4
VENT PIPE STRUCTURE
PENETRATION
ROOF
ROOF
AIR INTAKE PIPE STRUCTURE
PENETRATION
ROOF
ROOF
VENT PIPE SIZE
3”
4”
AIR INTAKE PIPE SIZE
4”
4”
MAXIMUM
VENT
PIPE
LENGTH
BWC150
49.5 FT
N.R.
BWC225
N.R.
47 FT
MAXIMUM INT
AKE
PIPE LENGTH
BWC150
52 FT
N.R.
BWC225
N.R.
52 FT
EXHAUST TERMINAL
RODENT SCREEN BY VENT SYSTEM
MANUFACTURER. SAME DIAMETER
AS VENT SYSTEM. SEE TABLE 6.5.
AIR INTAKE TERMINAL
4” 180 ELBOW
4” 180 ELBOW
VENT MATERIAL
APPROVED VENT SYSTEM SHOWN
IN TABLE 6.5
AIR INTAKE MATERIAL
GALVANIZED OR PVC
“N.R” - Not recommended “N.A.” - Not applicable
Summary of Contents for BIMINI BWC225
Page 2: ......
Page 22: ...20 PAGE INTENTIONALLY LEFT BLANK ...
Page 23: ...21 PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...22 PAGE INTENTIONALLY LEFT BLANK ...
Page 29: ...Figure 8 3 Piping Method 1 Heat Indirect Water Heater 27 ...
Page 37: ...Figure 9 1 Wiring Connections Diagram 35 ...
Page 38: ...Figure 9 2 Ladder Diagram 36 ...
Page 39: ...Figure 9 3 Wiring of Isolation Relay for Control of Two Heating Circulators 37 ...
Page 56: ...54 PAGE INTENTIONALLY LEFT BLANK ...
Page 60: ...58 ...
Page 61: ...59 ...
Page 62: ...60 ...
Page 63: ...61 Gas Train Assembly Honeywell Valve ...
Page 64: ...Gas Train Assembly Dungs Valve 62 ...
Page 66: ...64 ...
Page 68: ...66 ...
Page 69: ...67 ...
Page 70: ...68 ...
Page 72: ......