© 2022 All rights reserved. Data subject to change without notice.
47
Rev. B | 2022.03
LPT-M - Operation Manual
Press ENTER to access the screen and use the ARROW keys to increase or
decrease the number. Press ENTER to move to the next digit and again to save
and Exit the screen.
To set the Relay OFF DELAY:
In the Hardware Configuration Menu (passcode 1001), press either ARROW
to scroll through the menu and select Program Relay. Press ENTER to select.
Scroll through the menu and choose Relay Delay OFF.
Press ENTER to access the screen and use the ARROW keys to increase or
decrease the number. Press ENTER to move to the next digit and again to save
and Exit the screen.
NOTE:
The ON Delay and OFF Delay are entered in seconds. The maximum
length of time that either can be set to is 9999 (2.7 hours). The default setting
from the factory is 0000 seconds, indicating no ON or OFF Delays are set.
6.9.3 Relay Mode of Operation (Normal or FAILSAFE)
The LPT-M is designed to be fail-safe so the relay is normally energized in a
non-alarm state for failsafe operation. If required, the LPT-M can be configured
for normal relay operation.