© 2022 All rights reserved. Data subject to change without notice.
43
Rev. B | 2022.03
LPT-M - Operation Manual
the backlight of the display will flash on and off. The alarm and the flashing
display can be stopped for a period of time by pressing the ENTER button.
6.8.1 Enable / Disable Audible
The factory default for the buzzer setting is ENABLED.
In the Hardware Configuration Menu (passcode 1001), press either ARROW to
scroll through the menu and select Program Audible. Press ENTER to select.
Scroll through the menu and choose Audible Enable. Press ENTER to choose
between ON or OFF.
6.8.2 Audible ON Delay
You can set the buzzer to be delayed in sounding for a specified period of time
after the LPT-M has gone into an alarm state. If the alarm state is neutralized
before the time delay expires, the device returns to normal operation.
In the Hardware Configuration Menu (passcode 1001), press either ARROW to
scroll through the menu and select Program Audible.