38
3.3.12
Thermal compensation
STP-UNI-2.8 and STP-UNI-5.0 temperature probes enable the compensation of Absorption voltage and Floating
Voltage depending on the ambient temperature of the battery room.
The coefficient used is -18mV/°C for 12V model and -36mV/°C for 24V models.
Temperature is not compensated when wintering (or standby sealed bat),
stabilized DC power supply and lithium iron phosphate (LiFePO4)
with BMS settings are selected.
Option not compatible with option temperature protection.
3.3.13
temperature protection
STP-ALT-2.4 temperature probes enable the protection
from a
temperature too high.
Option not compatible with option thermal compensation.
3.3.14
CAN-Bus
The regulator offers two receptacles matching with connectors Molex Microfit 3.0, 6 circuits (reference 43025-0600).
Documentation n° 1336205REG_CAN (hardware and software specification) is available upon request.
3.3.15
Remote display
The battery MPPT supports the remote tactile color display UNI-DISPLAY-R.
3.3.16
Remote control
This option G-ON/OFF-R allows you to shut down the remote MPPT from a two-wire cable.
The converter is stopped if both wires are short-circuited
3.3.17
Factory setting
The MPPT's factory settings are:
sealed Lead, BOOT OFF
To define the charge in function of your battery, please refer to the chart, paragraph: 3.3.2.
For special batteries, call a professional installer, who will make the specific settings in accordance with the battery
manufacturer's specifications and according to the specifics of the installation.
CRISTEC is not liable for any damage caused to the batteries or for inefficient recharging.