background image

2

FnIO G-Series

Copyright(C) CREVIS Co.,Ltd S82-31-899-4599 URL: www.crevis.co.kr

DOCUMENT CHANGE SUMMARY

REV

PAGE

REMARKS

DATE

EDITOR

1.0

New Document

19/01/16

JY,Hyun

Summary of Contents for GT-3901

Page 1: ...1 FnIO G Series Copyright C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr Version 1 0 2018 CREVIS Co Ltd GT 3901 User Manual Analog Input Module ...

Page 2: ...2 FnIO G Series Copyright C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr DOCUMENT CHANGE SUMMARY REV PAGE REMARKS DATE EDITOR 1 0 New Document 19 01 16 JY Hyun ...

Page 3: ...ule List 6 3 Specification 7 3 1 GT 3901 7 3 1 1 Wiring Diagram 7 3 1 2 LED Indicator 8 3 1 3 Channel Status LED 8 3 1 4 Environment Specification 9 3 1 5 Specification 10 3 1 6 Updata cycle of process data 11 3 1 7 Mapping Data Into the Image Table 12 3 1 8 Parameter Data 22 4 Dimension 26 4 1 GT 3901 RTB 26 5 Mounting 27 5 1 I O Inserting and Removing Devices 27 5 2 RTB RemovableTerminal Block 2...

Page 4: ... Do not assemble the products and wire with power applied to the system Else it may cause an electric arc which can result into unexpected and potentiallydangerousaction by field devices Arching is explosion risk in hazardous locations Be sure that the area is non hazardousor remove system power appropriatelybefore assembling or wiring the modules Do not touch any terminalblocks or IO modules when...

Page 5: ...quipment certified for U S and Canada See UL File E235505 CE Certificate EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions Reach RoHS EU CHINA Identifiesinformationabout practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss Identifiesinformation that is critical for successful a...

Page 6: ...6 FnIO G Series Copyright C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr 2 Analog Input Module List GT Number Description ID GT 3901 3Phase AC Measurement Lx Ly 500Vac 1A 3901 ...

Page 7: ...cation 3 1 GT 3901 3 1 1 Wiring Diagram Pin No Signal Description Signal Description Pin No 0 Voltage Input 0 L1 VoltageInput 1 L2 1 2 Voltage Input 2 L3 VoltageInput Common Neutral 3 4 Current Input L1 Current Input N1 5 6 Current Input L2 Current Input N2 7 8 Current Input L3 Current Input N3 9 ...

Page 8: ...ut LED OFF Error Occurred Current Input LED Green Normal Operation No Signal Voltage Input LED OFF Current Input LED OFF Error Occurred Voltage Input LED Green Current Input LED Green Normal Operation G Bus Status Status LED OFF Disconnection Status LED Green Connection Please refer to Input Image Data Error Byte LED No LED Function Description LED Color 0 Status Green 1 Voltage Input Channel 1 Gr...

Page 9: ...000m Mounting DIN Rail General Specification Shock Operating IEC 60068 2 27 Vibration Resistance Sine Vibration Based on IEC 60068 2 6 5 25Hz 1 6mm 25 300Hz 4g Sweep Rate 1 Oct min 20 Sweeps Random Vibration 10 40 Hz 0 0125 g2 Hz 40 100 Hz 0 0125 0 002 g2 Hz 100 500 Hz 0 002 g2 Hz 500 2000 Hz 0 002 1 3 x 10 4g2 Hz Test time 1hrs for each test EMC Resistance Burst ESD EN 61000 6 2 2005 EN61000 6 4 ...

Page 10: ...rrent Power Energy Frequency Power Factors Measuring error Voltage Current 0 5 20 50 Voltage Currnet 1 20 60 Voltage Currnet 1 5 20 70 Freauency 0 1Hz Phase angle 0 6 General Specification Power Dissipation Max 125 mA 5Vdc Isolation I O to Logic PhotocouplerIsolation Field power Non Isolation Field Power Supply Voltage 24Vdc nominal Voltage Range 18 32Vdc Power Dissipation 0mA 32Vdc Wiring I O Cab...

Page 11: ...Max Rms Current 300us Min Rms Current 300us Apparent Power 250us Active Power 350us Max Active Power 350us Min Active Power 350us Reactive Power 2000us ApparentEnergy 100ms Total ApparentEnergy 100ms Active Energy 100ms Total Active Energy 100ms Reactive Energy 100ms Total Reavitve energy 100ms Cos phi 200us SupplyNetwork Frequency 200us Max SupplyNetwork Frequency 200us Min SupplyNetwork Frequenc...

Page 12: ... Byte Output Data Input Data 0 Control byte 0 Status byte 0 1 Control byte 1 Status byte 1 2 Control byte 2 Status byte 2 3 Control byte 3 Status byte 3 4 Not used Error byte 0 5 Error byte 1 6 Error byte 2 7 Reserved 8 Process value 1 9 10 11 12 Process value 2 13 14 15 16 Process value 3 17 18 19 20 Process value 4 21 22 23 ...

Page 13: ...ID CON_ID Status byte 1 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 reserved Measure Select CON_ID Measure select 0 Voltage 1 Current 2 Power 3 PF 4 Phase Angle 5 Frequency 6 Energy 7 reserved CON_ID CON_ID Status byte 2 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 reserved Measure Selcet CON_ID Measure Select 0 Voltage 1 Current 2 Power 3 PF 4 Phase Angle 5 Frequency 6 Energy 7 reserved CO...

Page 14: ...age Input ERROR 0 OK 1 Error occurred Error byte 1 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 ERR_IL1 IL1_Error code ERR_VL3 VL3_Error code ERR_VL3 Phase 3 Voltage Input ERROR 0 OK 1 Error occurred ERR_IL1 Phase 1 Current Input ERROR 0 OK 1 Error occurred Error byte 2 BBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 ERR_IL3 IIL3_Error code ERR_IL2 IL2_Error code ERR_IL2 Phase 2 Current Input ...

Page 15: ...Bit 1 Bit 0 Proc0 23 16 Proc0 23 16 Process value 0 of Status Byte 0 Process value 0 3 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Proc0 31 24 Proc0 31 24 Process value 0 of Status Byte 0 Process value 1 0 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Proc1 7 0 Proc1 7 0 Process value 1 of Status Byte 1 Process value 1 1 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Proc1 15...

Page 16: ...ss value 2 of Status Byte 2 Process value 2 2 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Proc1 23 16 Proc2 23 16 Process value 2 of Status Byte 2 Process value 2 3 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Proc1 31 24 Proc2 31 24 Process value 2 of Status Byte 2 Process value 3 0 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Proc3 7 0 Proc3 7 0 Process value 3 of Status...

Page 17: ...CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr Proc3 23 16 Process value 3 of Status Byte 3 Process value 3 3 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Proc3 31 24 Proc3 31 24 Process value 3 of Status Byte 3 ...

Page 18: ..._ID CON_ID Control byte 1 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 reserved Measure Select CON_ID Measure select 0 Voltage 1 Current 2 Power 3 PF 4 Phase Angle 5 Frequency 6 Energy 7 reserved CON_ID CON_ID Control byte 2 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 reserved Measure Selcet CON_ID Measure Select 0 Voltage 1 Current 2 Power 3 PF 4 Phase Angle 5 Frequency 6 Energy 7 reserved...

Page 19: ...oltage L1 N Uint32 0 01V 07 Min RMS Voltage L2 N Uint32 0 01V 08 Min RMS Voltage L3 N Uint32 0 01V 09 reserved 0A 0B 0C 0D 0E 0F CON_ID Measured Value Data Type Scaling Measure Select Current 00 RMS Current L1 N Uint32 0 001A 01 RMS Current L2 N Uint32 0 001A 02 RMS Current L3 N Uint32 0 001A 03 Max RMS Current L1 N Uint32 0 001A 04 Max RMS Current L2 N Uint32 0 001A 05 Max RMS Current L3 N Uint32...

Page 20: ...eactive power L2 Int32 0 01VAR 0E Reactive power L3 Int32 0 01VAR CON_ID Measured Value Data Type Scaling Measure Select Energy 00 Apparent energy L1 Uint32 Set the Parameter 01 Apparent energy L2 Uint32 02 Apparent energy L3 Uint32 03 Total Apparent Energy Uint32 04 Active energy L1 Int32 05 Active energy L2 Int32 06 Active energy L3 Int32 07 Total Active Energy Int32 08 Reactive Energy L1 Int32 ...

Page 21: ...ork frequency L1 uint32 0 01Hz 04 Max Supply network frequency L2 uint32 0 01Hz 05 Max Supply network frequency L3 uint32 0 01Hz 06 Min Supply network frequency L1 uint32 0 01Hz 07 Min Supply network frequency L2 uint32 0 01Hz 08 Min Supply network frequency L3 uint32 0 01Hz 09 reserved 0A 0B 0C 0D 0E CON_ID Measured Value Data Type Scaling Measure Select Phase angle 00 Phase angle phi L1 uint32 0...

Page 22: ...the current transformer ratio divisor 1 55 65Hz 1 0 01 Wh VARh VAh 2 0 1 Wh VARh VAh 3 1 Wh VARh VAh 4 0 01k Wh VARh VAh 5 0 1k Wh VARh VAh 6 1k Wh VARh VAh 7 reserved Byte 2 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 3 Bit 2 Bit 1 Overvoltage threshold Lx value Resolution 0 2V Overvoltage threshold 250V value 0 2V MAX 300V Byte 3 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 3 Bit 2 Bit 1 Undervoltage threshold Lx va...

Page 23: ...et the correct Power Factor Energy the reactive power measurement is negative when the load is capacitive and when the load is inductive The sign of the reactive power can therefore be used to reflect the sign of the power factor Power Factor Sign Fundamental Reactive Power abs Active Power Apparent Power ...

Page 24: ...alue CT sensor 1 x 12 bit 001111101000 bit Set CT 1000 Scaling for energy values 3 bit 000 bit Set 1 m Wh VARh VAh Frequency 1 bit 1 bit Set 55 65Hz Overvoltage Threshold Lx 8 bit 00110010 bit Set 260V Undervoltage threshold Lx 8 bit 00000000 bit Set 0V default Overcurrent Threshold Lx 8 bit 00000000 bit Set 0 8A default All of Parameter E8 83 32 00 00 Byte hex Setp 2 Set the Control Byte See Outp...

Page 25: ...Byte 0 RES Measure Select Current CON_ID Rms Current L1 N 0 0 0 1 0 0 0 0 Status Byte 0 RES Measure Select Power CON_ID Apparent Power L1 0 0 0 2 0 0 0 0 Status Byte 0 RES Measure Select Power CON_ID Active Power L1 0 0 0 2 0 0 1 1 Step 4 Check the Process value Process value 0 Rms Voltage 000055F0 Dword hex 22000 Dec 220V Process value 0 Rms Current 000F4240 Dword hex 1000000 Dec 1000A Process va...

Page 26: ...26 FnIO G Series Copyright C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr 4 Dimension 4 1 GT 3901 RTB mm ...

Page 27: ...Perform work on devices only if they are de energized Working on energized devices can damage them Therefore turn off the power supply before working on the devices 5 1 I O Inserting and Removing Devices As above figure in order to safeguard the G Series module from jamming it should be fixed onto the DIN rail with locking level To do so fold on the upper of the locking lever To pull out the G Ser...

Page 28: ...o kr 5 2 RTB Removable Terminal Block Whole terminal block can be combined and removed for the convenience There is a locking switch on the RTB for the easy combination and easy removal Easy combination and easy removal for IO modules on the din rail through One Touch Locking Switch ...

Page 29: ... of the bus modules is carried out via the internal bus It is comprised of 6 data pin and 2 field power pin Please refer to the table below regarding the pin description from P1 to P8 No Description P1 System Power VCC P2 System Power GND P3 GBUS TX P4 GBUS TX P5 GBUS RX P6 GBUS RX P7 Field Power GND P8 Field Power VCC Do not touch data and field power pins in order to avoid soiling and damage by ...

Reviews: