CAEN-BLOCK-CENCN-2-POE
Ethernet to Cresnet
®
Bridge for CAEN Automation Enclosures
Installation & Operation Guide
Description
The Crestron
®
CAEN-BLOCK-CENCN-2-POE is an Ethernet to Cresnet bridge that
provides control with a Crestron Automation Enclosure (CAEN). The device is controlled
and powered by LAN PoE (Power over Ethernet). The CAEN-BLOCK-CENCN-2-POE can
control and power all modules in the cabinet and also the devices on the Cresnet network.
CAEN-BLOCK-CENCN-2-POE Specifications
Installation
WARNING
: To avoid fire, shock, or death, turn off the power at the circuit breaker or
fuse and test that the power is off before wiring!
NOTE
: Observe the following points:
• Install and use this product in accordance with appropriate electrical codes and
regulations.
• A licensed electrician should install this product.
NOTE
: Before using the CAEN-BLOCK-CENCN-2-POE, ensure the device is using the
latest firmware. Check for the latest firmware for the CAEN-BLOCK-CENCN-2-POE at
www.crestron.com/firmware. Load the firmware onto the device using Crestron
Toolbox™ software.
NOTE
: Unless otherwise indicated, the lighting system specified in this guide is
modular, requiring assembly in the field by a licensed electrician, in accordance with all
national and local codes.
If an assembled UL Listed panel is required, Crestron offers this service through its UL
Listed panel shop. This includes complete in-factory system configuration and assembly
by Crestron for an additional fee.
Additional Resources
Visit the product page on the Crestron website (www.crestron.com)
for additional information and the latest firmware updates. Use a QR
reader application on your mobile device to scan the QR image.
Mount and Wire the CAEN-BLOCK-CENCN-2-POE
Mount the CAEN-BLOCK-CENCN-2-POE in accordance with all national and local codes.
Use the two 8B x 1/4” screws, supplied, to attach the CAEN-BLOCK-CENCN-2-POE to an
enclosure. The first illustration below shows the CAEN-BLOCK-CENCN-2-POE mounted in
a single-wide enclosure; the second illustration shows the double-wide enclosure.
NOTE
: The equipment is only to be connected to PoE networks without routing to
outside plants.
* The 24 Vdc power supply must be capable of delivering 75 W to the load when plugged in alone or
while in conjunction with the PoE or PoE+.
** If another power supply is used, the power supply must be UL or cUL Listed or have equivalent NRTL
certification with the minimum power ratings shown, have an LPS output, and be rated for use in an
ambient temperature of 40 °C.
Replace the Divider
NOTE
: Class 1 and Class 2 wiring must be separated. Ensure that the correct divider is
used.
Replace the divider.
1. Remove the two screws that secure the divider in the enclosure. Discard the screws
and the divider.
2. Using the supplied screws and nuts, secure the new divider to the side of the
enclosure.
SPECIFICATION
DETAILS
Power
Power over Ethernet
IEEE 802.3at Type 1 PoE and Type 2
PoE+ Powered Device; refer to “Minimum
Power Ratings”
Cresnet Power
24 Vdc; refer to “Minimum Power Ratings”
Minimum Power Ratings
Input Source
PoE Class 0 (12.95 W)
using an 802.3at
Type 1 (or 802.3af) PSE
10 W Power to Load (NET B)
PoE+ Class 4 (25.5 W)
using an 802.3at
Type 2 PSE
20 W Power to Load (NET B)
24 Vdc Power Input*
75 W Power to Load (NET B)
Environmental
Temperature
32° to 104 °F (0° to 40 °C)
Humidity
10% to 90% RH (noncondensing)
Enclosure
Metal, gray, surface-mount module with (2)
integral mounting flanges; installs in a
Crestron CAEN, CAEN-MLO, or CAENIB
enclosure
Available Power Supplies**
(sold separately)
PWE-4803RU
CEN-SWPOE-16
CNPWS-75
CNPWSI-75
LEFT
RIGHT
SINGLE WIDTH CABINET
DOUBLE WIDTH CABINET
PWR
NET
MSG
RESET
SETUP
TEST
LAN PoE
OVER RIDE
POWER
INPUT
OVR
OVR
NET B
24
G
G
G
NET A
24 Y Z G
TYPICAL CRESNET
CONNECTION
C A E N - B LO C K- C E N C N - 2 - P O E
E T H E R N E T T O C R E S N E T B R I D G E
LEFT
RIGHT
SINGLE WIDTH CABINET
DOUBLE WIDTH CABINET
PWR
NET
MSG
RESET
SETUP
TEST
LAN PoE
OVER RIDE
POWER
INPUT
OVR
OVR
NET B
24
G
G
G
NET A
24 Y Z G
TYPICAL CRESNET
CONNECTION
C A E N - B LO C K- C E N C N - 2 - P O E
E T H E R N E T T O C R E S N E T B R I D G E
NOTE
: When installing the CAEN-BLOCK-CENCN-2-POE in a single-wide enclosure,
use the gray module interconnect cable to make the connection between the module
and the RIGHT port on the CAEN-BLOCK-CENCN-2-POE.
NOTE
: When installing the CAEN-BLOCK-CENCN-2-POE in a double-wide enclosure,
use the red module interconnect cable to make the connection between the right
module and the RIGHT port on the CAEN-BLOCK-CENCN-2-POE. Use the gray module
interconnect cable to make the connection between the left module and the LEFT port
on the CAEN-BLOCK-CENCN-2-POE.