CLW-DIM, DIMS, & SLVD(W/A/B)

 

Multigang Installations 

approved connectors (supplied by others) to 
make Class 2 connections inside the wallbox. 

In multigang installations, several controls are grouped 
horizontally in one wallbox. For a smooth appearance, 
one-piece multigang faceplates (not supplied) can be 
installed. 

• 

CAUTION

:  TO REDUCE THE RISK OF 

OVERHEATING AND POSSIBLE DAMAGE 
TO OTHER EQUIPMENT, DO NOT INSTALL 
TO CONTROL A RECEPTACLE OR A 
MOTOR OPERATED APPLIANCE (i.e. BATH 
FAN). 

1.  When combining controls in a wallbox, remove 

inner side sections prior to wiring (refer to the 
following figure). 

• 

Wiring: Use copper wire only. For supply 
connections, use wires rated for at least 75°C. 

Inner Sections of Multiganged Switches 

DO NOT REMOVE OUTER SECTIONS

REMOVE INNER SECTIONS

 

• 

Lamp Type: The -DIM, -DIMS, and -SLVD are 
designed for use with permanently installed 
incandescent, magnetic low voltage, or tungsten-
halogen only.  

• 

Temperature: The -DIM, -DIMS, and -SLVD are 
designed to be used where temperatures are 
between 32° to 104°F (0° to 40°C). 

• 

Wallboxes: Devices mount in standard 
wallboxes. For easy installation, Crestron 
recommends using 3 ½” deep wallboxes. Several 
devices can be installed in one wall box 
(multigang). This requires the removal of side 
sections (refer to diagram on page 3) and the 
derating of the dimming device. For a smooth 
appearance, one-piece multigang faceplates (not 
supplied) can be installed. 

The load capacity must also be derated. The following 
charts provide derating information for various 
applications. 

• 

Other Switch Devices: Mechanical 3- or 4-way 
switches will not work with the -DIM, -DIMS, or 
-SLVD. 

Derating Information for Incandescent and Tungsten Halogen 
Applications 

• 

Spacing: If mounting one device above another, 
leave at least 4 ½” vertical space between them. 

Part

Number

No Side Removed 

One Side 

Removed 

Two Sides 

Removed 

-DIM 1000W 

600W  400W 

-DIMS 

1000W 

600W 

400W 

-SLVD 

No Derating Necessary 

• 

Low Voltage Applications: Use with core and 
coil (magnetic) low voltage transformers only. 
Do not use any solid-state electronic low voltage 
transformers. 
 
Operation of a low voltage circuit with all lamps 
inoperative or removed may result in current 
flow in excess of normal levels. To avoid 
transformer overheating and premature 
transformer failure, Crestron recommends the 
following: 

Derating Information for Magnetic Low Voltage Applications

*

 

Part 

Number 

No Side 

Removed 

One Side 

Removed 

Two Sides 

Removed 

-DIM 

1000VA/750W  

600VA/450W  

400VA/300W  

-DIMS 

1000VA/750W  

600VA/450W  

400VA/300W  

-SLVD 

No Derating Necessary 

*  VA ratings are for input power to the transformer. If you do not 

know the input power requirement of the transformer, use the bulb’s 
wattage rating to determine proper rating. 

 

Do not operate low voltage circuits 
without operative lamps in place. 

2.  To remove a side section, bend the side section 

back and forth with a pair of pliers until the 
section breaks off from the mounting plate. Use a 
file or sandpaper to remove any excess metal. 

 

Replace burned-out lamps as quickly as 
possible. 

 

Use transformers that incorporate 
thermal protection or fuse transformer 
primary windings to prevent 
transformer failure due to overcurrent. 

Prewire for Master Application 

Each device has two Class 2 low voltage wires (plus a 
ground wire) that provide a Cresnet connection over 

Installation Guide – DOC. 5995B 

Stand Alone Wall Box Dimmer:  CLW-DIM, DIMS, & SLVD  

  3  

 

Summary of Contents for CLW-DIM

Page 1: ...ion mode selection switch Refer to Operating Buttons and Switches on page 5 for more information In the absence of Cresnet communications the dimmer can still be used to control lighting The CLW DIMS DIMS is similar to the DIM with the added capability of working with a slave unit CLW SLVD in a multi switch single circuit application The CLW SLVD SLVD is a slave unit that when used in conjunction ...

Page 2: ...d Front Industry Compliance This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc Important Notes Read before installation Codes Install in accordance with all local and national electrical codes Alternate wiring methods may be used for the Class 2 wiring connection The 2002 National Electrical Code Article 725 55 prohibits Class 2 conductors of the DI...

Page 3: ...h the DIM DIMS or SLVD Derating Information for Incandescent and Tungsten Halogen Applications Spacing If mounting one device above another leave at least 4 vertical space between them Part Number No Side Removed One Side Removed Two Sides Removed DIM 1000W 600W 400W DIMS 1000W 600W 400W SLVD No Derating Necessary Low Voltage Applications Use with core and coil magnetic low voltage transformers on...

Page 4: ...tion of the Crestron website http www crestron com dealer tech_resources design_center hot_design_tips_and_ diagrams tech_sales_tips NOTE The BLACK wire Cresnet ground should not be grounded with the GREEN Ground wire on the DIM DIMS SLVD CLW DIM CLW DIMS Wiring NOTE Crestron recommends using Crestron s Cresnet DM cable for connecting the DIM and DIMS to the Cresnet network NOTE The DIM and DIMS r...

Page 5: ...ed using the two small buttons to raise right button and lower left button the lighting level NOTE The RED Load and BLACK Hot wires are 14 AWG The BLUE Slave and WHITE Neutral wires are 18 AWG The GREEN Ground wire is 16 AWG The GRAY Cresnet wires are 22 AWG The BLACK wire Cresnet ground paired with the GRAY Cresnet wires is 22 AWG If the lighting level is to be stored as a preset move the mode se...

Page 6: ...o CRESTRON 6 Volvo Drive Rockleigh N J or its authorized subsidiaries with RMA number clearly marked on the outside of all cartons Shipments arriving freight collect or without an RMA number shall be subject to refusal CRESTRON reserves the right in its sole and absolute discretion to charge a 15 restocking fee plus shipping costs on any products returned with an RMA 3 Return freight charges follo...

Reviews: