- 9 -
16
Refit the elements by carefully feeding the tails down
through the hole in the base insulation, ensuring the
tab is pointing forward. Fit the front layer of cells with the
flat side toward the front of the radiator. Ensure that the tab
on the element is captured below the bottom row of cells
and that the element is vertical.
16
A
16
C
17
Replace the inner front complete with insulation by
locating its bottom edge behind the front lip of the
chassis and inserting the retaining screws along the top
and both sides.
18
Check that the screws securing the radiator to the
wall have been fully tightened. It is essential that all
screws are replaced to ensure earth continuity.
Once installed
DO NOT
attempt to
reposition the radiator without first
unloading the energy retention cells
and obtaining the services of a
competent electrician.
17
16
B
19
In its factory default setting, the radiant element will
be allowed to operate for up to 2 hours after the
beginning of the off-peak charge period to maintain a
comfortable room temperature if required. After 2 hours the
radiant element will be automatically disabled until the end
of the off-peak charge period.
In circumstances where it will not be necessary to maintain
a high ambient room temperature between the hours of
typically 12am and 2am (for example a commercial
application), this feature can be disabled by removing the
time delay pin on the power enable board (see Fig. 19
B
),
which will automatically switch the radiant element off at the
beginning of the off-peak charge period.
19
A
19
B
RADIANT ELEMENT OVERRIDE