A.3.
WARNING Notices
WARNING Notices call attention to actions that have the potential of causing damage to a
program, device, system or data.
WARNING
The installation of an “on-line” Uninterruptible Power Supply (UPS) is strongly recommended
to ensure continuity of service and to protect the equipment in the event of a mains failure.
WARNING
The primary floor must bear a minimum load of 1000 daN/m
2
.
WARNING
In the case of very heavy systems, it is recommended to add freely set, flat headed, hydraulic
jacks under the raised floor prior to installing the system.
WARNING
To avoid incorrect handling, the equipment must be removed from its packing by authorized
Customer Service Engineers only.
WARNING
If the air-conditioning system is shut down, “operational” conditions must be re-established,
in compliance with temperature (3
°
per hour) and hygrometry (5% per hour) gradients, AT
LEAST ONE HOUR before powering up equipment.
WARNING
Do not place perforated / damper slabs in the immediate vicinity of one or more
air-conditioning units, as shown in the following figure.
WARNING
Cables must be correctly labeled at both ends.
WARNING
To protect from condensation at heat exchanger level, it is strongly recommended to insulate
the water pipes.
Appendix A. Notices
A-5