A.2.
CAUTION Notices
CAUTION Notices call attention to the presence of hazards that have the potential of
causing moderate or minor personal injury.
CAUTION
The equipment must be transported as indicated on packing labels.
The equipment may be extremely heavy and require the use of an elevator.
The Data Processing Site manager must allocate enough personnel to ensure safe handling of
the equipment.
CAUTION
It is mandatory for layout to take the safety of personnel into account. Access for stretchers
must be provided around equiment and cabinets.
CAUTION
The lanes must be at least 80 cm wide to allow passageway for stretchers.
CAUTION
It is strongly recommended not to use CO
2
gas (hazard to personnel and to equipment). The
use of HALON 1301 gas is prohibited as from January 1 2003.
CAUTION
A raised floor compliant with the Standards NF P67 103-1 and 103-2 in force is mandatory,
in particular for the installation of a Cooling Unit).
CAUTION
If the air-conditioning unit(s) is (are) placed on brackets in the room, it is mandatory to
electrically isolate these brackets from the raised floor slabs, crossbeams, and actuators.
CAUTION
To ensure the maximum service life of air-water exchangers, chilled water must comply with
the VGB chilled water regulations (VGB-R 455P). Chilled water used must be soft enough to
prevent deposits, but must not be so soft that heat exchanger corrosion occurs.
CAUTION
An air-conditioning system, compliant with the requirements of NF X44-101,
Class 4 000 000 and with ISO 7730, is recommended.