VCIOM-05044
Page 45 of 75
DIgITal EPIC-2 TEChnICal Manual
InstallatIon and operatIng InstructIons
next the user is asked if the valve is already
closed. The user has the option of aborting
by simultaneously pressing the up and Down
arrow keys or continue by pressing EnTER.
If continue, the Calibration will proceed to the
next screen. (See Figure 64).
This is generally a very quick operation, so the
above screen will appear as 100% Done-Pass.
If it did not pass, an error message will be
displayed. The error must be corrected for
the calibration to pass.
FIguRE 64
Performing low calibration
FIguRE 65
accessing high calibration
FIguRE 66
Performing high calibration
7.3.3.5 High position calibration
This calibration method allows the user to
perform only the upper end of the position
(100%) without affecting any other parameters
within the full calibration like the lower end
position, pressure readings, speed etc. The
user MuST have completed either the full
device controlled or full user controlled
calibration before performing this calibration.
This calibration is useful in the case where
after performing the full device/user controlled
calibration, the user observes drift in the
position for the upper end over the time due
to change in temperature, pressure, magnets
degrading or weakening actuator spring or
lose valve shaft coupler. The valve must be
in appropriate position before starting this
calibration.
Refer to Figure 65
From Calibration Menu, scroll down to “high
Calib” then press SElECT/EnTER. The lCD
will display the screen shown in Figure 65.
This asks the user if they wish to continue. The
user has the option of selecting “no” or “Yes”
by using the Down arrow key to switch. If “no”,
it will terminate the Calibration before even
starting. If “Yes”, the Calibration will proceed to
the next screen.
next the user is asked if the valve is already
opened. The user has the option of aborting
by simultaneously pressing the up and Down
arrow keys or continue by pressing EnTER.
If continue, the Calibration will proceed to
the next screen. (See Figure 66).
This is generally a very quick operation, so the
above screen will appear as 100% Done-Pass.
If it did not pass, an error message will be
displayed. The error must be corrected for the
calibration to pass.