VCIOM-05044
Page 23 of 75
DIgITal EPIC-2 TEChnICal Manual
InstallatIon and operatIng InstructIons
segment
description
1
Valve type (rotary or linear)
2
Product name (DEPIC-2)
3
Current date (Month/Day,Year) This is the only format supported
4
Current time (hh:MM) The time is always displayed in 24 hours
5
This area will usually be blank but will have the text “Fix” above the ma to indicate the device is
currently in fixed current mode. If the text “Fix” doesn’t appear, it means the transmitter output
current reflects the current position of the valve.
6
Position/ma text (%Open or %Close)
7
Temperature unit (°F or °C)
8
Valve position usually 0% to 100%
9
Transmitter output current usually 4 ma-20 ma
10
Temperature value
11
number of active alarms
12
Current active process or current device status
This area is used to display the current running process if there is any otherwise it display the
status of last maintenance PST. Each message has a priority and gets displayed based on its
priority if there are multiple status messages active at a time. The priority 0 is the highest and 3
is the lowest.
Message name
Message description
Priority
ESD-On
The device is into ESD mode
0
Cal-On
The device is into calibration mode
0
SIgn-On
The device is into FST mode
0
PST-On
The device is into PST mode
0
SOVT-On
The device is into SOVT mode
0
SET ClOCK
The clock is not configured
1
KYPD-lOCK
The keypad is locked by haRT
1
Run Cal
The device doesn’t have valid calibration.
1
Cal-FaIl
The last calibration failed with an error
2
Run BSIgn
There is no baseline signature performed yet
1
BSIgn-FaIl
The baseline signature failed with an error
2
Run BPST
The baseline PST is not performed yet
1
Run MPST
The maintenance PST is not performed yet
1
MPST-FaIl
The last maintenance PST was failed
2
SOVT-FaIl
The last SOVT failed with an error
2
OK
There is no error, device has been configured and
running properly
3