BASIN INFORMATION (Cont.)
Method of Cable Entry into Basin:
Direct Burial Cable W/Cord Grips
Conduit Coupling
Cable Sizes(s) from Control Panel to Basin:
(Example: 10/4 power cable and Two 18/4 Control Cables)
Valve at Sewer Main:
Check Valve
Manual shut Off Valve
JUNCTION BOX INFORMATION
Is Junction Box Dry:
YES
NO
Are All Cord Grips Tight:
YES
NO
Is Junction Box Cover Tight:
YES
NO
Are All Wire Connections Tight:
YES
NO
Are Pump Cords Away from Pump:
YES
NO
CONTROL PANEL INFORMATION
Is Interior Dry:
YES
NO
Are All Connections Tight:
YES
NO
Is Control Panel Mounted Securely:
YES
NO
COMPLETE THIS SECTION ONLY IF A PANEL NOT SUPPLIED BY BARNES IS BEING USED
Panel Manufactured by
Model Number:
Short Circuit Protection Type:
Circuit Breaker
Fuse
None
Short Circuit Protection Amp Rating(s):
Amps
Overload Protection Amp Rating:
Amps
Overload Protection Model:
Do Protection Devices Comply with Pumps Amp Rating:
YES
NO
ELECTRICAL CHECK
Single Phase:
Voltage Supply at Panel Line Connection with Pump Off:
L1-L2_______Volts
(Must be within 10% Pump Rated Volts)
Three Phase:
Voltage Supply at Panel Line Connection with Pump Off:
L1-L2______Volts
L2-L3________Volts
L3-L1________Volts
(Must be within 10% Pump Rated Volts)
ALL PUMPS:
Resistance of Pump Power Connections at Control Panel Terminal Strip with Power Off:
+
Red/Black
Ohms, Black/White
Ohms, Red/White
Ohms.
NOTE:
Resistance Readings must be within 5%, compare to chart in pump operation manual.
Resistance Between Ground Lug in Panel and Outside Pump Case/Rail:
NOTE:
Resistance Reading Should Indicate Less Than 1 Ohm.
Ohms.