Spares and Accessories
Connection tubes.
Binder-style adaptors.
Mechseal-style adaptors.
Temperature gauges.
Pressure gauges.
Replacement strainers.
Carrycases.
Replacement Hex Keys
Please ‘Contact Us’ for further information and options.
Technical Specification
Measurement Range/Accuracy
0.5-200 kPa Differential Measurement.
10 bar Maximum Static Pressure.
0.5 to 10 kPa, Accuracy = +/- 0.1 kPa.
10 to 200 kPa, Accuracy = +/- 1.0% Reading.
Effective Operating Time
20 hours with standard Alkaline PP3 battery.
Calibration
Factory calibration is carried out in controlled conditions, using calibration equipment which is traceable
to National Standards.
Generally, it is recommended that ProComm handsets are serviced and calibrated annually. However, this
is not a fixed period and more frequent service intervals may be necessary for extremely high-use meters
or for meters which are regularly used on very dirty systems or on systems that contain high
concentrations of cleaning agents / treatments.
Valve Database
The ProComm unit is pre-programmed with more than 4500 valves in its database.
Please note: whilst every effort is made to ensure that the valve data contained within the
ProComm is correct, valve manufacturers invariably reserve the right to modify their products,
without notice, and so Crane cannot be held responsible for any inaccuracies or omissions. The
user is advised to check t h e performance data (Kvs values) of specific valves prior to use.
User Interface
The ProComm unit is fitted with a memory card for holding data. There is not normally any reason for
accessing the data on this card. Contact Crane for more information if valve data is to be updated as
there are some important procedures to be followed to edit the data correctly.
15