background image

11

10.  Before removing the pump from the basin, be sure to
 

close the shut-off valve. (This prevents back

fl

 ow from

 

the pressure sewer.)

11.  Make sure level controls are provided at time of
 installation.
12.  Recommended starts per hour, 6 to 8, no more than
 10.

D-3) Start-Up Report:

Included at the end of this manual are two start-up report 
sheets, these sheets are to be completed as applicable. 
Return one copy to Barnes and store the second in the 
control panel or with the pump manual if no control panel 
is used. It is important to record this data at initial start-
up since it will be useful to refer to should servicing the 
pump be required in the future.

D-3.1) Identi

fi

 cation Plate:

Record the numbers from the pump’s identi

fi

 cation plate 

on both START-UP REPORTS provided at the end of the 
manual for future reference.

D-3.2) Insulation Test:

Before the pump is put into service, an insulation 
(megger) test should be performed on the motor. The 
resistance values (ohms) as well as the voltage (volts) 
and current (amps) should be recorded on the start-up 
report.

D-3.3) Pump-Down Test:

After the pump has been properly wired and lowered into 
the basin, sump or lift station, it is advisable to check 
the system by 

fi

 lling with liquid and allowing the pump 

to operate through it’s pumping cycle. The time needed 
to empty the system, or pump-down time along with the 
volume of water, should be recorded on the start-up 
report.

SECTION E: PREVENTATIVE MAINTENANCE

As the motor and seal chambers are oil 

fi

 lled, no 

lubrication or other maintenance is required, and 
generally Barnes pumps will give very reliable service 
and can be expected to operate for years on normal 
sewage pumping without failing. However as with any 
mechanical piece of equipment a preventive maintenance 
program is recommended and suggested to include the 
following checks:

1)   Test moisture detector control “Test Switch” for
 

continuity of circuit. - Water in the seal chamber will

 

energize a seal leak warning light at the control panel.

 

This is a warning light only and does not stop the 

 

motor. It indicates the seal has leaked and must be

 

repaired. This should be done as soon as possible to

 

prevent further damage. See section D-2.3.

2)  Inspect impeller and body for excessive build-up or
 

clogging and repair as required per section F-3.

3)  Check motor for ground leakage and proper amp
 

draw. See section D-3.2.

4)  Inspect outer seal for wear or leakage and repair as
 

required per section F-4.

SECTION F: SERVICE AND REPAIR
NOTE

: All item numbers in ( ) refer to Figures 8 & 9 for 

2HP and 10 & 11 for 3, 5 & 7.5HP Pumps.

WARNING! - Electrical power to the pump 
motors must be disconnected and locked out 
to prevent any dangerous electrical hazards 
or personnel danger before any service work 
is done to the pump.

CAUTION! - operating pump builds 
up heat and pressure; allow time for 
pump to cool to room temperature 
before handling or servicing.

F-1) Motor & Shaft Seal Service

WARNING! -  Motor & upper shaft seal repair:
Motor and upper shaft seal must only 
be serviced at the BARNES factory.  Any 
unauthorized 

fi

 eld repair voids warranty.

The XSGV Submersible Pump motor is designed to meet 
the requirements for Underwriters Laboratory Class I, 
Group D service and must only be serviced as described 
above.

F-2) Conduit Box and Cable Assembly:

WARNING ! - The conduit box and cable 
assembly should not be 

fi

 eld serviced. If a 

problem develops in the power or control 
cord the complete pump should be removed 
and serviced only by authorized personnel as 
described above.

F-3) Impeller, Cutters and Volute Service:
F-3.1) Disassembly and Inspection:

To obtain access to the impeller (13) or shredding ring 
(9), 

fi

 rst remove screw (6) and washer (7). Then holding 

the motor shaft stationary with a screwdriver, tap the 
radial cutter (8) loose in the counter-clockwise direction 
and remove, (Heat may be needed to break the screw (6) 
loose.)

Next remove nuts (3) and washers (4) from stud (2) and 
pull the body (1) and square ring (5) from the rest of the 
pump. Remove shims (12) from shaft, then impeller (13) 
can be removed by turning it counter-clockwise while 
holding stationary the motor shaft with a screwdriver. 

NOTE:

 With the impeller (13) removed, the seal spring is 

relaxed and some oil may seep from the seal cavity. 

DO 

NOT

 store this pump without the impeller (13) in place to 

hold the seal shut.

Summary of Contents for Barnes XSGV 2 HP

Page 1: ...umps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 082188 Rev V Series XSGV 2 3 5 7 5HP 60Hz 3450RPM For Class I Group D Division 1 Underwriters Laboratories Inc File No E73842 Canadian St...

Page 2: ...VE MAINTENANCE 11 F SERVICE and REPAIR 11 13 G REPLACEMENT PARTS 13 TROUBLE SHOOTING 14 CROSS SECTION 2HP Fig 8 15 EXPLODED VIEW 2HP Fig 9 16 PARTS LIST 17 CROSS SECTION 3 5 7 5HP Fig 10 18 EXPLODED VIEW 3 5 7 5HP Fig 11 19 PARTS LIST 20 ELECTRICAL DATA 21 SUSPENDED SYSTEM Fig 12 22 NON SPARKING MOVABLE for 2HP Fig 13 23 NON SPARKING MOVABLE for 3 5 7 5HP Fig 14 24 RETURNED GOODS POLICY 25 WARRANT...

Page 3: ...hip under pressure WARNING DO NOT wear loose clothing that may become entangled in the impeller or other moving parts WARNING Keep clear of suction and discharge openings DO NOT insert fingers in pump with power connected Make sure lifting handles are securely fastened each time before lifting Do not operate pump without safety devices in place Always replace safety devices that have been removed ...

Page 4: ... be included in control panel Requires Barnes Starter or Control Panel which Includes Capacitors or Capacitor pack THREE PHASE Dual Voltage 230 460 Requires Overload Protection to be Included in control panel MOISTURE SENSORS Normally Open N O Requires relay in control panel TEMP SENSORS Normally Closed N C Requires relay in control panel OPTIONAL EQUIPMENT Seal Material Impeller Trims Cord Length...

Page 5: ...cluded in control panel Requires Barnes Starter or Control Panel which Includes Capacitors or Capacitor pack THREE PHASE Dual Voltage 230 460 Requires Overload Protection to be Included in control panel MOISTURE SENSORS Normally Open N O Requires relay in control panel TEMP SENSORS Normally Closed N C Requires relay in control panel OPTIONAL EQUIPMENT Seal Material Impeller Trims Cord Length inche...

Page 6: ... Center check your Barnes representative or Crane Pumps Systems Inc Service Department in Piqua Ohio telephone 937 778 8947 or Crane Pumps Systems Canada in Brampton Ontario 905 457 6223 SECTION C INSTALLATION C 1 Location These self contained pumping units are Underwriters Laboratory Listed for Class I Group D Division 1 Locations and are recommended for use in a sump lift station or basin This p...

Page 7: ...alternator switching system will be required for a duplex system A high level alarm may be required to alert maintenance personnel A low level cut off may be required to provide system shutdown if the main level control system malfunctions The off or low level float should be positioned so that the liquid level never drops below the minimum submergence level see Fig 1 C 4 Electrical Connections WA...

Page 8: ...rature Sensor And Moisture Detection System Must Be Connected To The Motor Circuitry Such That The Motor Will Be De energized If Excessive Motor Temperatures Are Reached And or If Water Is Detected In The Oil And or Motor Chamber Failure To Have The Above Mentioned Systems Installed And Operative Nullifies Warranty C 4 3 Overload Protection The normally closed N C thermal sensor is embedded in the...

Page 9: ...e source of this condition should be determined and rectified before the pump is put back into normal operation DO NOT LET THE PUMP CYCLE OR RUN IF AN OVER LOAD CONDITION OCCURS If current through the temperature sensor exceeds the values listed an intermediate control circuit relay must be used to reduce the current or the sensor will not work properly TYPICAL THERMAL PROTECTION WIRING DIAGRAM FI...

Page 10: ...r motor rotation can result in poor pump performance and can damage the motor and or pump To check the rotation suspend the pump freely momentarily apply power and observe the kickback Kickback should always be in a counter clockwise direction as viewed from the top of the pump motor housing D 2 1 Incorrect Rotation for Three Phase Pumps In the event that the rotation is incorrect for a three phas...

Page 11: ...e motor It indicates the seal has leaked and must be repaired This should be done as soon as possible to prevent further damage See section D 2 3 2 Inspect impeller and body for excessive build up or clogging and repair as required per section F 3 3 Check motor for ground leakage and proper amp draw See section D 3 2 4 Inspect outer seal for wear or leakage and repair as required per section F 4 S...

Page 12: ... shaft stationary with screwdriver and tighten Then replace washer 7 and screw 6 Radial cutter 8 to be flush with shredding ring 9 on suction side to within 020 F 4 OUTER SHAFT SEAL SERVICE CAUTION Handle seal parts with extreme care DO NOT scratch or mar lapped surfaces F 4 1 Disassembly and Inspection Outer Seal To expose outer shaft seal 17 for examination disassemble volute cutter and impeller...

Page 13: ...ALWAYS furnish the following information 1 Pump serial number and date code Paragraph G 4 2 Pump model number Paragraph G 3 3 Pump part number Paragraph G 2 4 Part description 5 Item part number 6 Quantity required 7 Shipping instructions 8 Billing Instructions G 2 PART NUMBER The part number consists of a six 6 digit number which appears in the catalog A one or two letter suffix may follow this n...

Page 14: ...k cutter for freedom of operation security and condition Clean cutter and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Remove examine for damage Replace pump stator if required 11 Repair fixtures as required to eliminate leakage 12 Check pump temperature limits fl...

Page 15: ...15 FIGURE 8 2HP XSGV SERIES ...

Page 16: ...16 FIGURE 9 2HP XSGV SERIES ...

Page 17: ...ze 5 62 Dia STD 067552TD 5 00 Dia 067552TE 4 88 Dia 067552TF 4 75 Dia 067552TG 4 62 Dia 067552TH 4 50 Dia 067552TJ 4 38 Dia 067552TK 4 25 Dia 067552TL 4 12 Dia 067552TM 4 00 Dia 067552TN 3 88 Dia 067552TP 3 75 Dia 067552TR 3 62 Dia 067552TS 3 50 Dia 14 1 082134 Lifting Handle 15 2 1 130 1 Hex Hd Cap Screw 5 16 18 x 1 50 lg Stainless 16 1 Motor Assy Includes Motor 30 ft Cable C C B Inner Outer Seal...

Page 18: ...18 FIGURE 10 3 5 7 5HP XSGV SERIES ...

Page 19: ...19 FIGURE 11 3 5 7 5HP XSGV SERIES ...

Page 20: ...Dia STD for 3HP 132462TN 4 88 Dia 132462TP 4 75 Dia 132462TQ 4 62 Dia 132462TR 4 50 Dia 132462TS 4 38 Dia 132462TT 4 25 Dia 132462TU 4 12 Dia 132462TV 4 00 Dia 14 1 082165 Lifting Handle 15 2 1 319 1 Hex Hd Cap Screw 7 16 14 x 2 lg Stainless 16 1 Motor Assy Includes Motor 30 Ft Cable and C C B Inner Outer Seals 128622 3HP 200V 1PH XSGV3002L 128623 3HP 230V 1PH XSGV3022L 128624 3HP 200V 3PH XSGV306...

Page 21: ...79 XSGV5032L 5 230 3 60 3450 L 21 9 120 0 10 4 SOW 0 745 19 0 84 1 00 XSGV5042L 5 460 3 60 3450 L 11 0 60 0 10 4 SOW 0 745 19 4 00 3 74 XSGV5052L 5 575 3 60 3450 L 8 8 46 0 10 4 SOW 0 745 19 5 12 XSGV7532L 7 5 230 3 60 3450 J 22 3 136 0 10 4 SOW 0 745 19 0 93 0 87 XSGV7542L 7 5 460 3 60 3450 J 11 2 68 0 10 4 SOW 0 745 19 3 72 3 28 XSGV7552L 7 5 575 3 60 3450 G 8 2 45 0 10 4 SOW 0 745 19 0 86 Windi...

Page 22: ...shers b and tighten Attach the pump cover to the top of the bracket Then connect the discharge pipe by others to the pump Mount the float switches to the discharge pipe and pull the pump cord sets and the float switch cords through the cord grips attached to the pump cover The pump with cover can now be lowered into basin PARTS LIST ITEM QTY PART No DESCRIPTION 61 1 071753 Suspended Bracket Basin ...

Page 23: ... NPT x 14 Lg 52 1 077881 Ball Check Valve Cast Iron 1 1 4 NPT 53 2 075476 Close Nipple Stainless 1 25 NPT 54 1 075481 Elbow Stainless 1 25 NPT x 90 55 1 075485 Moveable Fitting Brass 56 1 074758 Upper Pump Bracket Stainless 59 1 074759 U Bolt and Nuts Pump NOT included under this part number The Non Sparking Moveable Assembly will be factory assembled to pump when a Basin Package system is ordered...

Page 24: ...s 2 NPT x 90 6 1 075486 Moveable Fitting Brass 7 1 076107 Pipe Stainless 2 NPT x 6 Lg 8 1 075276 U Bolt and Nuts Stainless 3 8 16 x 4 5 Lg 9 A R Loctite PST567 10 A R Loctite 242 11 2 1 40 1 Hex Hd Cap Screw Stainless 3 8 16 X 2 Lg 12 2 15 23 1 Hex Nut Stainless 3 8 16 13 4 082727 Flat Washer Stainless 3 8 14 2 026210 Flange 15 1 069140 Gasket 16 1 083690 Pipe Nipple Stainless 2 NPT x 3 5 Lg Pump ...

Page 25: ...PXVW EH VLJQHG E RXU DXWKRUL HG UHSUHVHQWDWLYH XH WR LQDFFXUDFLHV LQ HOG WHVWLQJ LI D FRQÀ LFW DULVHV EHWZHHQ WKH UHVXOWV RI HOG WHVWLQJ FRQGXFWHG E RU IRU XVHU DQG ODERUDWRU WHVWV FRUUHFWHG IRU HOG SHUIRUPDQFH WKH ODWWHU VKDOO FRQWURO 5 200 1 7 216 25 63 33 7 216 25 7 26 5 68 7 1 520 6 67 06 1 6 6 1 9 8 7 216 21 8 7 6 21 285 67 9 3 5 1 1 38 6 1 8675 1 250 7 21 68 5 200 1 7 216 2 127 2167 787 55 1...

Page 26: ...nt To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration Form go to http www cranepumps com ProductRegistration If you have a claim under the provision of the warranty contact your local Crane Pumps...

Page 27: ...__ Type _________________________________ Number and size of short circuit device s ___________ Amp rating ___________________ Overload Type _____________ Size ______________ Amp rating ___________________ Do protection devices comply with pump and motor Amp rating YES___ NO___ Are all electrical and panel entry connections tight YES___ NO___ Is the interior of the panel dry YES___ NO___ Liquid le...

Page 28: ... OHYHO FRQWUROV LQVWDOOHG DZD IURP WXUEXOHQFH 6BBB 12BBB V OHYHO FRQWURO RSHUDWLQJ SURSHUO 6BBB 12BBB V SXPS IXOO VXEPHUJHG GXULQJ RSHUDWLRQ 6BBB 12BBB ROORZ XS RUUHFWLYH FWLRQ 5HTXLUHG 6BBB 12BBB GGLWLRQDO RPPHQWV BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Reviews: