5
MODEL
NO
HP
VOLT PH/Hz RPM
(Nom)
NEMA
START
CODE
FULL
LOAD
AMPS
LOCKED
ROTOR
AMPS
CORD
SIZE
CODE
TYPE
CORD
O.D.
± .02 (.5)
in (mm)
WINDING
RESISTANCE
MAIN -- START
PGPH2022L
2
240
1 / 60
3450
H
15.0
53.8
12/3
SOW
.61 (15.5)
1.5 -- 5.1
PGPP2022L
2
240
1 / 60
3450
H
15.0
53.8
12/3
SOW
.61 (15.5)
1.5 -- 5.1
Winding Resistance ± 5%, measured from terminal block. Pump rated for operation at ± 10% voltage at motor.
Recommended Breaker & Heater Sizes
Pump Model
HP Phase
Volts
Breaker Size
All PGP
Series Pumps
2
1
240
25 AMP
The nameplate is located on top of the pump. This contains the pumps part number, horsepower voltage, phase, and
serial number, as well as other information. The start-up form located in the back of this manual contains a place to
record this data. The information should be recorded now so the pump does not have to be pulled again later. The
start-up form can be left in the control panel until station start-up is completed later.