background image

9

TROUBLE SHOOTING

CAUTION !

 Always disconnect the pump from the electrical power source before handling.

If the system fails to operate properly, carefully read instructions and perform maintenance recommendations.
If operating problems persist, the following chart may be of assistance in identifying and correcting them:

MATCH “CAUSE” NUMBER WITH CORRELATING “CORRECTION” NUMBER

.

NOTE:

 Not all problems and corrections will apply to each pump model.

PROBLEM

CAUSE

CORRECTION

Pump will not run

1.

 Poor electrical connection, blown fuse, 

tripped breaker or other interruption of power, 
improper power supply.

2.

 Motor or switch inoperative (to isolate 

cause, go to manual operation of pump).

2a.

 Float movement restricted.

2b. Switch will not activate pump or is defec-
tive.

3a.

 Insuf

fi

 cient liquid level.

3b. Switch is unable to activate

1. Check all electrical connections for 
security. Have electrician measure current 
in motor leads, if current is within ±20% 
of locked rotor Amps, impeller is probably 
locked. If current is 0, overload may be 
tripped. Remove power, allow pump to cool, 
then recheck current.
2a. Reposition pump or clean basin as 
required to provide adequate clearance for 

fl

 oat.

2b. Disconnect level control. Set ohmmeter 
for a low range, such as 100 ohms full scale 
and connect to level control leads. Actuate 
level control manually and check to see that 
ohmmeter shows zero ohms for closed switch 
and full scale for open switch. (Float Switch).
3a. Make sure liquid level is at least equal to 
suggested turn-on point.
3b. Rotate ESPS level control in horizontal 
position.
4. Recheck all sizing calculations to 
determine proper pump size.
5. Check discharge line for restrictions, 
including ice if line passes through or into 
cold areas.
6. Remove and examine check valve for 
proper installation and freedom of operation.
7. Open valve.
8. Check cutter for freedom of operation, 
security and condition. Clean cutter and inlet 
of any obstruction.
9. Loosen union slightly to allow trapped air 
to escape.Verify that turn-off level of switch 
is set so that the suction is always 

fl

 ooded. 

Clean vent hole.
10. Remove & examine for damage. Replace 
pump stator if required.
11. Repair 

fi

 xtures as required to eliminate 

leakage.
12. Check pump temperature limits & 

fl

 uid 

temperature.
13. Replace portion of discharge pipe with 

fl

 exible connector.

14. Turn to automatic position.
15. Check for leaks around basin inlet and 
outlets.

Pump will not turn off

2a. Float movement restricted.
2b. Switch will not activate pump or is defec-
tive.
4. Excessive in

fl

 ow or pump not properly sized 

for application.
9. Pump may be airlocked.
14. H-O-A switch  on panel is in “HAND” posi-
tion

Pump hums but does not run

1. Incorrect voltage
8. Cutter jammed or loose on shaft, worn or 
damaged, inlet plugged.

Pump delivers insuf

fi

 cient capacity

1. Incorrect voltage.
4. Excessive in

fl

 ow or pump not properly sized 

for application.
5. Discharge restricted.
6. Check valve stuck closed or installed 
backwards.
7. Shut-off valve closed.
8. Cutter jammed or loose on shaft, worn or 
damaged, inlet plugged.
9. Pump may be airlocked.
10. Pump stator damaged/torn.

Pump cycles too frequently or runs 
periodically when 

fi

 xtures are not in use

6. Check valve stuck closed or installed 
backwards.
11. Fixtures are leaking.
15. Ground water entering basin.

Pump shuts off and turns on indepen-
dent of switch, (trips thermal overload 
protector). 

CAUTION!

  Pump may start 

unexpectedly. Disconnect power supply.

1. Incorrect voltage.
4. Excessive in

fl

 ow or pump not properly sized 

for application.
8. Cutter jammed, loose on shaft, worn or 
damaged, inlet plugged.
12. Excessive water temperature.

Pump operates noisily or vibrates 
excessively

4. Operating at too high a pressure.
5. Discharge restricted.
8. Cutter broken.
13. Piping attachments to buiding structure too 
rigid or too loose.

Summary of Contents for Barnes PGPH Series

Page 1: ...Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 131469 Rev E Series PGPP PGPH 2 HP 3450 RPM 60 Hz High Flow and High Head INSTALLATION MANUAL Submersible Grinder Pump Professional Plumbing M...

Page 2: ...ING Keep clear of suction and discharge openings DO NOT insert fingers in pump with power connected Make sure lifting handles are securely fastened each time before lifting Do not operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Do not exceed manufacturers recommendation for maximum performance as this could cause the motor ...

Page 3: ...nder pump station The basin collects all wastewater from the house The solids in the sewage are then ground to a small size suitable for pumping in the slurry The grinder pump generates sufficient pressure to pump this slurry from your home to the wastewater plant Power Failure Your grinder pump cannot dispose of wastewater or provide an alarm signal without electrical power If electrical power se...

Page 4: ... N Hardware 300 series stainless steel CORD ENTRY 30 Ft 9 1m 15 Ft 4 5m Cord on Compact series CC CE CT Custom Molded Quick Connected for sealing and strain relief CORD CSA UL Approved 12 3 12 5 Type SOW SPEED 3450 RPM 60Hz nominal UPPER BEARING Design Single Row Ball Oil Lubricated Load Radial LOWER BEARING Design Single Row Ball Oil Lubricated Load Radial Thrust MOTOR Design NEMA L Single phase ...

Page 5: ...at 10 voltage at motor Recommended Breaker Heater Sizes Pump Model HP Phase Volts Breaker Size All PGP Series Pumps 2 1 240 25 AMP The nameplate is located on top of the pump This contains the pumps part number horsepower voltage phase and serial number as well as other information The start up form located in the back of this manual contains a place to record this data The information should be r...

Page 6: ...bowline knot where shown per the directions provided Steps 1 through 5 On the CT Not Shown series tie bowline knot on the eyebolt On the L and AUE series tie bowline knot on the lifting handle See Fig 1 FIGURE 1 ...

Page 7: ...on Ontario Canada 905 457 6223 INSTALLATION Location The pump is designed with pipe legs to keep a minimum of 3 inch clearance THIS PUMP MUST BE INSTALLED WITH A MINIMUM OF 3 INCHES CLEARANCE UNDER THE PUMP FOR THE ENTRANCE OF SEWAGE SOLIDS Discharge Assemble discharge piping or hose assembly whichever is required by your application to the pump Discharge piping should be as short as possible Both...

Page 8: ... female end of cord plug into housing bore aligning alignment mark with hole in terminal block see Figure 4 Tighten bolts on compression flange until flush with motor housing FIGURE 4 OGV L Single phase 240 Volt AC 60Hz L Series 12 3 SOW FIGURE 5 ...

Page 9: ...d freedom of operation 7 Open valve 8 Check cutter for freedom of operation security and condition Clean cutter and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Remove examine for damage Replace pump stator if required 11 Repair fixtures as required to eliminate l...

Page 10: ...10 FIGURE 6 ...

Page 11: ...10395SD Seal outer Silicon Carbide STD 22 A R Permatex Sealent 2C 23 1 016079 Shim set 24 3 Qts 029034 Cooling Oil Mtr Housing 25 1 095368 Square Ring 26 4 1 300 1 Screw 5 16 18 x 1 25 SS ITEM QTY PART NO DESCRITION 28 1 061143 Retaining Ring 29 1 Q10 36 E4 Ball Bearing Lower 31 1 108368A Motor 2HP 240 Volt 1 Phase w capacitors Ground wire Supplied with Upper Bearing 31A 1 115327A RC Capacitor Run...

Page 12: ...Notes ...

Page 13: ...PXVW EH VLJQHG E RXU DXWKRUL HG UHSUHVHQWDWLYH XH WR LQDFFXUDFLHV LQ HOG WHVWLQJ LI D FRQÀ LFW DULVHV EHWZHHQ WKH UHVXOWV RI HOG WHVWLQJ FRQGXFWHG E RU IRU XVHU DQG ODERUDWRU WHVWV FRUUHFWHG IRU HOG SHUIRUPDQFH WKH ODWWHU VKDOO FRQWURO 5 200 1 7 216 25 63 33 7 216 25 7 26 5 68 7 1 520 6 67 06 1 6 6 1 9 8 7 216 21 8 7 6 21 285 67 9 3 5 1 1 38 6 1 8675 1 250 7 21 68 5 200 1 7 216 2 127 2167 787 55 1...

Page 14: ...nt To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration Form go to http www cranepumps com ProductRegistration If you have a claim under the provision of the warranty contact your local Crane Pumps...

Page 15: ...__ Type _________________________________ Number and size of short circuit device s ___________ Amp rating ___________________ Overload Type _____________ Size ______________ Amp rating ___________________ Do protection devices comply with pump and motor Amp rating YES___ NO___ Are all electrical and panel entry connections tight YES___ NO___ Is the interior of the panel dry YES___ NO___ Liquid le...

Page 16: ... OHYHO FRQWUROV LQVWDOOHG DZD IURP WXUEXOHQFH 6BBB 12BBB V OHYHO FRQWURO RSHUDWLQJ SURSHUO 6BBB 12BBB V SXPS IXOO VXEPHUJHG GXULQJ RSHUDWLRQ 6BBB 12BBB ROORZ XS RUUHFWLYH FWLRQ 5HTXLUHG 6BBB 12BBB GGLWLRQDO RPPHQWV BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Reviews: