Crane Barnes 084605 Installation And Operation Manual Download Page 6

6

C-4) Electrical Connections:

C-4.1) Power & Control Cords:

The cord assembly mounted to the pump must not be 

modified in any way except for shortening to a specific 

application. Any splice between the pump and the control 

panel must be made in accordance with all applicable electric 

codes. It is recommended that a junction box, if used, be 

mounted outside the sump or be of at least Nema 4 (EEMAC-

4) construction if located within the wet well. 

DO NOT USE 

THE POWER OR CONTROL CORDS TO LIFT PUMP.

 

NOTE: The White Wire Is Not A Neutral Or Ground Lead. 

The Black, White And Red Leads Are Power Carrying

Conductors. The Green Lead Is For Connection To 

Ground.

  

C-4.2) Overload Protection :

C-4.2-1) Three Phase - 

The normally closed (N/C) thermal 

sensor is embedded in the motor windings and will detect 

excessive heat in the event an overload condition occurs. 

The thermal sensor will trip when the windings become too 

hot and will automatically reset itself when the pump motor 

cools to a safe temperature. It is recommended that the 

thermal sensor be connected in series to an alarm device to 

alert the operator of an overload condition, and/or the motor 

starter coil to stop the pump. In the event of an overload, the 

source of this condition should be determined and rectified 

immediately. 

DO NOT LET THE PUMP CYCLE OR RUN IF 

AN OVERLOAD CONDITION OCCURS ! 

C-4.2-2) Single Phase -

 The type of in-winding overload 

protector used is referred to as an inherent overheating 

protector and operates on the combined effect of temperature 

and current. This means that the overload protector will trip 

out and shut the pump off if the windings become too hot, 

or the load current passing through them becomes too high. 

It will then automatically reset and start the pump up after 

the motor cools to a safe temperature. In the event of an 

overload, the source of this condition should be determined 

and rectified immediately. 

DO NOT LET THE PUMP CYCLE 

OR RUN IF AN OVERLOAD CONDITION OCCURS ! 

NOTE:

 Single phase pumps can be orederd with an optional 

Thermal Sensor as well as the standard in winding overload 

protection. 

C-4.3) Moisture Sensors:

A normally open (N/O) detector is installed in the pump 

seal chamber which will detect any moisture present. It is 

recommended that this detector be connected in series to an 

alarm device or the motor starter coil to alert the operator that 

a moisture detect has occurred. In the event of a moisture 

detect, check the individual moisture sensor probe leads for 

continuity, ( ∞  resistance = no moisture ) and the junction 

box/control box for moisture content. The above situations 

may induce a false signal in the moisture detecting circuit. If 

none of the above test prove conclusive, the pump(s) should 

be pulled and the source of the failure identified and repaired. 

IF A MOISTURE DETECT HAS OCCURRED SCHEDULE 

MAINTENANCE AS SOON AS POSSIBLE. 

C-4.4) Wire Size:

Consult a qualified electrician for proper wire size if additional 

power cable is required. See table for electrical information.

TEMPERATURE SENSOR ELECTRICAL RATINGS

Volts

Continuous 

Amperes

Inrush 

Amperes

110-120

3.00

30.0

220-240

1.50

15.0

440-480

0.75

7.5

600

0.60

6.0

SECTION: D START-UP OPERATION

 

D-1) Check Voltage and Phase:

Before operating pump, compare the voltage and phase 

information stamped on the pump identification plate to the 

available power. 

D-2) Check Pump Rotation:

Before putting pump into service for the first time, the motor 

rotation must be checked. Improper motor rotation can 

result in poor pump performance and can damage the motor 

and/or pump. To check the rotation, suspend the pump 

freely, momentarily apply power and observe the “kickback”. 

“Kickback” should always be in a counter-clockwise direction 

as viewed from the top of the pump motor housing. 

D-2.1) Incorrect Rotation for Three-Phase Pumps:

In the event that the rotation is incorrect for a three-phase 

installation, interchange any two power cable leads at the 

control box. 

DO NOT

 change leads in the cable housing 

in the motor. Recheck the “kickback” rotation again by 

momentarily applying power. 

D-2.2) Incorrect Rotation for Single-Phase Pumps:

In the unlikely event that the rotation is incorrect for a single 

phase pump, contact a Barnes Service Center. 

D-3) Start-Up Report:

Included at the end of this manual is a start-up report sheet, 

this sheet is to be completed as applicable. Return one copy 

to Barnes and store the second in the control panel or with 

the pump manual if no control panel is used. It is important to 

record this data at initial start-up since it will be useful to refer 

to should servicing the pump be required in the future. 

D-3.1) Identification Plate:

Record the numbers from the pump identification plate on 

both START-UP REPORTS provided at the end of the manual 

for future reference. 

D-3.2) Insulation Test:

Before the pump is put into service, an insulation (megger) 

test should be performed on the motor. The resistance values 

(ohms) as well as the voltage (volts) and current (amps) 

should be recorded on the start-up report. 

D-3.3) Pump-Down Test

:

After the pump has been properly wired and lowered into the 

basin, sump or lift station, it is advisable to check the system 

by filling with liquid and allowing the pump to operate through 

its pumping cycle. The time needed to empty the system, or 

pump-down time along with the volume of water, should be 

recorded on the start-up report.

Summary of Contents for Barnes 084605

Page 1: ...onstant product improvement program product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 131290 Rev F Series 4SEV DS 4 5 15HP 1750RPM 60Hz ...

Page 2: ...15 PARTS LIST 16 18 RETURNED GOODS POLICY 19 WARRANTY 18 START UP REPORT 20 21 WARRANTY REGISTRATION 19 SPECIAL TOOLS AND EQUIPMENT INSULATION TESTER MEGGER DIELECTRIC TESTER SEAL TOOL KIT see parts list PRESSURE GAUGE KIT see parts list Other brand and product names are trademarks or registered trademarks of their respective holders Barnes is a registered trademark of Crane Pumps Systems Inc 1994...

Page 3: ...ert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Secure the pump in its operating position so it can not tip over fall or slide DO NOT exceed manufacturers ...

Page 4: ...uirrel Cage Induction Winding Class F Class H Rated Magnet Wire Service Factor 1 15 SINGLE PHASE Capacitor Start Capacitor Run Requires BARNES Starter Panel Which includes capacitors and overload protection THREE PHASE 200 240 480 is Tri voltage motor Requires overload protection to be included in control panel VFD Suitable MOISTURE SENSOR N O Requires relay in control panel TEMP SENSOR N C Requir...

Page 5: ...are self contained and are recommended for use in a sump lift station or basin This pump is designed to pump sewage effluent or other nonexplosive or noncorrosive wastewater and shall NOT be installed in locations classified as hazardous in accordance with the National Electrical Code NEC ANSI NFPA 70 or Canadian Electrical Code Never install the pump in a trench ditch or hole with a dirt bottom t...

Page 6: ...situations may induce a false signal in the moisture detecting circuit If none of the above test prove conclusive the pump s should be pulled and the source of the failure identified and repaired IF A MOISTURE DETECT HAS OCCURRED SCHEDULE MAINTENANCE AS SOON AS POSSIBLE C 4 4 Wire Size Consult a qualified electrician for proper wire size if additional power cable is required See table for electric...

Page 7: ...4SEV7534DS 140233 7 5 230 3 1750 D 26 8 80 0 8 4 SOW 0 83 21 0 71 4SEV7544DS 140234 7 5 460 3 1750 D 13 4 40 0 8 4 SOW 0 83 21 2 85 4SEV7554DS 140235 7 5 575 3 1750 D 10 7 32 0 10 4 SOW 0 75 19 1 4SEV11364DS 140236 11 3 200 3 1750 B 32 2 109 5 8 4 SOW 1 06 27 0 35 4SEV11334DS 140237 11 3 230 3 1750 D 28 0 126 0 8 4 SOW 1 06 27 0 35 4SEV11344DS 140238 11 3 460 3 1750 D 14 0 63 0 8 4 SOW 1 06 27 1 4...

Page 8: ...ean dry container In separate container drain seal chamber by removing pipe plug 22 2 Check oil for contamination using an oil tester with a range to 30 Kilovolts breakdown 3 If oil is found to be clean and uncontaminated measure above 15 KV breakdown refill the motor housing and seal chamber as per section F 1 3 4 If oil is found to be dirty or contaminated or measures below 15 KV breakdown the t...

Page 9: ... After removal of cable and box assembly 10 from motor housing 2 remove cable lead wires from motor lead wires and moisture and temperature sensors wires if equipped from control cable by removing connectors 12 and 17 The wiring connections should be noted to insure correct connections when reassembling Remove cap screws 19 Vertically lift the outside motor housing 2 from bearing bracket 21 with l...

Page 10: ...ve impeller 28 as outlined in paragraph F 2 1 Drain oil from seal chamber as outlined in paragraph F 1 3 Remove cap screws 8 and lifting strap 7 Set unit upside down on blocks to avoid damaging cords Remove socket head cap screws 39 and lift seal plate 25 vertically being cautious to avoid seal damage together with diaphragm 32 clamp 43 and outboard stationary member 46A of shaft seal 46 from bear...

Page 11: ...l pusher until retainer engages spring 46C and spring is compressed slightly Make sure spring 46C is properly engaged in both retainers Slide seal plate 25 over shaft onto bearing bracket 21 being careful not to damage outboard stationary member 46A and align holes for socket head cap screws 39 Thread socket head cap screws 39 into bearing bracket 21 and tighten Fill seal chamber with oil as outli...

Page 12: ... White 3 9 T4 T5 T6 Together THREE PHASE 480 600 VOLT AC THREE PHASE 480 600 VOLT AC Power Cable Power Cable Motor Lead Number Motor Lead Number Green Ground Green Black 1 Red 2 White 3 T4 T7 Together T5 T8 Together T6 T9 Together MOISTURE AND TEMPERATURE SENSORS MOISTURE AND TEMPERATURE SENSORS Control Cable Control Cable Lead Number Lead Number Green Ground Green Black P1 Temperature Sensor Whit...

Page 13: ...e design configuration This number is used for ordering and obtaining information G 3 MODEL NUMBER This designation consists of numbers and letters which repre sent the discharge size series horsepower motor phase and voltage speed and pump design This number is used for order ing and obtaining information G 4 SERIAL NUMBER The serial number block will consist of a six digit number which is specif...

Page 14: ...eller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Check rotation If power supply is three phase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures as...

Page 15: ...15 FIGURE 10 4SEV Pump Series ...

Page 16: ...10c 2 071431A Friction Ring For 7 5 11 3Hp 3Ph 15Hp 575V 10d 1 071430A Grommet For 7 5 11 3Hp 3Ph 15Hp 575V 10e 1 Control Cable Not Sold Separately 10f 1 051448 Gland Nut 10g 2 021531 Friction Ring 10h 1 066871 Grommet 10J 1 030169 Ground Screw 10 32 x 5 8 Lg Stainless 11 1 051937 Square Ring 12 5 016406 Connector 13 2 5 Gal 029034 Oil Motor Housing 35 oz Oil Seal Cavity 14 2 5 32 6 Machine Screw ...

Page 17: ...Sq x 1 00 lg Stainless 34 1 11 81 1 SKHD Screw 1 2 13 x 1 1 4 lg 18 8 stainless 35 1 4587 SS Impeller Washer 531 x 1 562 Stainless 36 2 001348 Shim 031 x 1 5 O D Impeller 37 2 001349 Shim 010 x 1 5 O D Impeller 39 2 036803 Soc Hd Cap Screw 1 4 20 x 3 4 lg Stainless 42 1 056668 Square Ring 43 1 022879 Diaphragm Clamp Ring 44 4 002203 Cap Screw 1 4 20 x 7 8 lg Steel 46 1 039485 Shaft Seal Both Ends ...

Page 18: ...TION Your product is covered by a warranty www cranepumps com downloadables CATALOGS_OIPMs Warranty 24MonthWarranty pdf If you have a claim under the provisions of the warranty contact your local Crane Pumps Systems Inc Distributor ...

Reviews: