70
Section 5.1: User Level Functions
5.1.1 Frequency Output Monitor
The drive frequency can be monitored via Keypad and Multifunction output
terminals.
VIA KEYPAD
Speed 1
[USE: Code No. 00]: 1st Speed
(Factory Default: 10.00 Hz)
Range: 0.00 - SER 15 Hz
The Keypad displays the drive frequency output to the motor once the RUN
command is initiated. When the drive is not in RUN mode, the frequency display
indicates the programmed speed 1 frequency.
VIA FREQUENCY METER TERMINAL (See Section 5.3.14)
5.1.2 Frequency Reference
Speed Sel [USE: Code No. 02]: Speed Sel
(Factory Default: 2 Step)
Range: 2 Step
2Step Inf Var
3 Step
3Step Inf Var
5 Step
Speed 2 [USE: Function No. 05]: 2nd Speed
(Factory Default: 60.00 Hz)
Range: 0.00 - SER 15 Hz
Speed 3 [USE: Function No. 06]: 3rd Speed
(Factory Default: 0.00 Hz)
Range: 0.00 - SER 15 Hz
Speed 4 [USE: Function No. 07]: 4th Speed
(Factory Default: 0.00 Hz)
Range: 0.00 - SER 15 Hz
Speed 5 [USE: Function No. 08]: 5th Speed
(Factory Default: 0.00 Hz)
Range: 0.00 - SER 15 Hz
The hoist speed references are set in the User Level. Speed 1 and 2 will be applied
when Speed Sel is set to 2 Step or 2 Step Infinitely Variable. Speed 1, 2, and 3 will
be applied when Speed Sel is set to 3 Step or 3 Step Infinitely Variable and Speed
1, 2, 3, 4 and 5 will be applied when Speed Sel is set to 5 Step. The value of these
speed points will be limited to the value of Maximum Frequency set in Freq. max
[SER: Code No. 15]. Generally, the maximum frequency is set to the maximum
motor allowed output speed.
For more information contact: Sievert Crane and Hoist, (708) 771-1600, [email protected], www.sievertcrane.com