INSTALLATION
3.2.2 - Drainage by horizontal balanced flue
(C
13
)
R
ecommendations
Horizontal balanced flue installation is
possible when the wall next to the boiler
leads to a well-ventilated area on the
outside.
Do not place the flue terminal at the
front of the building or in an access
area (possible obstruction).
The horizontal balanced flue can be fit-
ted to the right or lefthand side or di-
rectly to the rear of the boiler and can
cross a wall-thickness of 1 metre maxi-
mum.
Two balanced flue terminals from two
separate boilers, positioned side by si-
de, must be separated by a minimum
distance of 0.
3
metres.
When installing the horizontal balanced
flue, use a 2% upward grade towards
the outside for the combustion product
tube.
To make assembly easier, apply liquid
soap over 5 cm of the section of the
tube to be fitted.
3.2.2.1 - 1 m horizontal balanced flue kit
(option)
See kit assembly guide
3.2.2.2 - 1 m polypropylene concentric flue
extensions (option)
3.2.2.3 - Polypropylene concentric bends
(option)
Note:
- Each 90° bend added reduces the total autho-
rised length by 1 m
3.2.2.4 - Adapting collar for the horizontal
balanced flue
- Standard balanced flue length:
L = 1 m
- Maximum linear length of horizontal flue:
Lmax =
4 m
Reference
Length
mm
V00.15225
1000
!
525-13-0
Fig. 26
Reference
Length
mm
Æ
int.
mm
Æ
ext.
mm
V00.17572
1000
75
110
Reference
Bend type
Æ
int.
mm
Æ
ext.
mm
V00.17573
90°
75
110
Reference
Æ
int.
mm
V00.15249
110
525-11-0
Fig. 27
525-25-0
Fig. 28
THR-25-0
Fig. 29