56
12.
FminTripTI (S)
Class I Min. grid
frequency trip time
{0.08, 300, 600.00}
13.
V.MaxRecover
Max. grid voltage recover
value
{208.0, 225, 249.0}
14.
V.MinRecover
Min. grid voltage recover
value
{104.0, 186, 208.0}
15.
V.RecoverT (S)
Grid voltage recover time
{0.08, 300, 600.00}
16.
F.MaxRecover
Max. grid frequency
recover value
{50.00, 60.4, 62.00}
17.
F.MinRecover
Min. grid frequency
recover value
{58.00, 59.4, 60.00}
18.
F.RecoverT
Grid frequency recover
time
{0.08, 300, 600.00}
19.
PVStartVol (V)
PV startup voltage
{150.0, 295, 310.0}
20.
SoftStep (KW/S)
Soft step
{0.1, 0.1, 1}
(2) “2 Restart” menu. If an internal fault shutdown happens, a severe fault
has occurred inside the inverter. The user may perform a force restart once in
this menu if the user needs to restart the inverter.
(3) “3 Recover” menu, the manufacturer’s parameter default value can be
INSTRUCTION:
The “Restart” function is effective only when the fault
“IntFault0010-0150” in the troubleshooting table occurs. The inverter
may restore to normal operation automatically if alarm or protection
faults occur. This function will not respond when the inverter is in
operation mode and a “FaultOperated” alarm interface will be
indicated.