ROUTINE MAINTENANCE

Filter Maintenance- the CR700 is equipped with a 100-mesh screen filter.  This filter should be checked 

periodically.  A partially clogged filter will slow down the recovery rate of this unit.

Check the filter cartridge as follows:  

• Use a 5/8” socket or boxed end wrench to loosen the suction port as shown in Figure 1.

• Once loose, remove the suction port- filter cartridge as shown in Figure 2.

• Either clean the current cartridge or replace with new cartridge.

• Inspect O-ring.  Re-lubricate with compressor oil or equivalent.

• Place filter cartridge back into suction port fitting.

• Hand tighten this assembly back onto the CR700.

• Use a 5/8” socket or boxed end wrench to tighten 1/8 of a turn.

Do not over tighten, damage to the O-ring may occur.

• Check the connection for leaks.

Figure 1

Figure 2

Learn more about automotive A/C tools and equipment we have.

Summary of Contents for PRO-SET CR700 Series

Page 1: ...EL ONLY 1 HP Commercial Refrigerant Recovery System OPERATION MANUAL TABLE OF CONTENTS Specifications Introduction General Safety Instructions Direct Liquid or Vapor Recovery Operation Liquid Push Pull Operation Routine Maintenance 2 2 3 3 4 4 5 ENGLISH 1 5 ...

Page 2: ...harge gauge to handle R 410A Small physical size Automatic Low Pressure cutout switch Integrated easy to use carrying handle and Safety bar 550 psig High Pressure cutout switch Easy and secure filter accesses No dangling filters to be damaged Models Compressor Type Dimensions Weight Operating Temperature Range Power Source Power Consumption Suction Pressure Gauge Discharge Pressure Gauge Filtratio...

Page 3: ...athing high concentration levels may cause heart arrhythmia loss of consciousness or even cause suffocation DANGER ELECTRICAL SHOCK HAZARD Always disconnect power source when servicing this equipment DANGER EXPLOSION RISK Do not recovery flammable refrigerants CAUTION all hoses may contain liquid refrigerant under pressure Contact with refrigerant may cause frostbite or other related injuries Wear...

Page 4: ...CLEARING position The CR700 will resume operation automatically The CR700 is now clearing out the condensor The CR700 will automatically shut off when a 10 hg vacuum is achieved Note If the LP override switch is set to ON position the unit will run continuously RECOVERY AND SELF CLEARING ARE COMPLETE LIQUID PUSH PULL OPERATION 1 Connect the unit as shown in Diagram 2 Note The recovery tank must be...

Page 5: ...ure 1 Once loose remove the suction port filter cartridge as shown in Figure 2 Either clean the current cartridge or replace with new cartridge Inspect O ring Re lubricate with compressor oil or equivalent Place filter cartridge back into suction port fitting Hand tighten this assembly back onto the CR700 Use a 5 8 socket or boxed end wrench to tighten 1 8 of a turn Do not over tighten damage to t...

Reviews: