DIRECT LIQUID OR VAPOR OPERATION

1. Connect the unit as shown in Diagram 1.

Note: The recovery tank must be rated for 38 bar.

2. Open the vapor valve on the Recovery Tank.

3. Open DISCHARGE valve on CR700.

Note: The Suction valve should be closed at this time.

4. Rotate the center valve to the “RECOVERY” position.

5. Push the Main Power Switch “ON”.

Note: If the unit fails to start, make sure there is no

suction pressure on the suction side of the unit. The 

compressor is designed to start against high differential 

pressures. Pressure on the suction side will reduce this 

differential. Reset Circuit Breaker  if tripped. Push the 

LP Override Switch to the “ON” position.

6. Once unit has started, open the SUCTION valve on the CR700 to start the refrigerant flow.

7. The CR700 is designed to directly recover large amounts of liquid refrigerant. If during liquid recovery the

compressor begins to make a slugging or hammering noise, meter the incoming liquid by closing the

suction valve until the noise subsides.

8. The CR700 will automatically shut off* when a 10”hg vacuum is achieved. If the pressure rises (due to

boiling liquid refrigerant) the CR700 will resume operation.

9. After the CR700 has shut off, rotate the center valve to the SELF-CLEARING position. The CR700 will

resume operation automatically. The CR700 is now clearing out the condensor. The CR700 will

automatically shut off* when a 10”hg vacuum is achieved.

Note: If the LP override switch is set to “ON” position the unit will run continuously.

RECOVERY AND SELF-CLEARING ARE COMPLETE

LIQUID PUSH-PULL OPERATION

1. Connect the unit as shown in Diagram 2.

Note: The recovery tank must be rated for 38 bar.

2. Open the liquid and vapor valve on the Recovery Tank.

Note: The Suction valve should be closed at this time.

3. Open the DISCHARGE valve on CR700.

4. Rotate the center valve to the “SELF-CLEARING”

position.

5. Push the Main Power Switch “ON”

Note: If the unit fails to start, make sure there is no suction 

pressure on the suction side of the unit. The compressor 

is designed to start against high differential pressures. 

Pressure on the siction side will reduce this differential. 

Reset Circuit Breaker  if tripped. Push the LP Override 

Switch to the “ON” position.

6. Once unit has started, open the SUCTION valve on the CR700 to start the vapor refrigerant flow.

7. Monitor the optional inline sight glass for liquid refrigerant movement.

8. Once the liquid refrigerant is no longer present, close SUCTION valve. The CR700 will automatically shut

off* when a 10”hg vacuum is achieved.

9. Proceed to Direct Vapor Recovery Operation. (prior page)

Note: If the LP override switch is set to “ON” position the unit will run continuously.

Summary of Contents for PRO-SET CR700 Series

Page 1: ...EL ONLY 1 HP Commercial Refrigerant Recovery System OPERATION MANUAL TABLE OF CONTENTS Specifications Introduction General Safety Instructions Direct Liquid or Vapor Recovery Operation Liquid Push Pull Operation Routine Maintenance 2 2 3 3 4 4 5 ENGLISH 1 5 ...

Page 2: ...harge gauge to handle R 410A Small physical size Automatic Low Pressure cutout switch Integrated easy to use carrying handle and Safety bar 550 psig High Pressure cutout switch Easy and secure filter accesses No dangling filters to be damaged Models Compressor Type Dimensions Weight Operating Temperature Range Power Source Power Consumption Suction Pressure Gauge Discharge Pressure Gauge Filtratio...

Page 3: ...athing high concentration levels may cause heart arrhythmia loss of consciousness or even cause suffocation DANGER ELECTRICAL SHOCK HAZARD Always disconnect power source when servicing this equipment DANGER EXPLOSION RISK Do not recovery flammable refrigerants CAUTION all hoses may contain liquid refrigerant under pressure Contact with refrigerant may cause frostbite or other related injuries Wear...

Page 4: ...CLEARING position The CR700 will resume operation automatically The CR700 is now clearing out the condensor The CR700 will automatically shut off when a 10 hg vacuum is achieved Note If the LP override switch is set to ON position the unit will run continuously RECOVERY AND SELF CLEARING ARE COMPLETE LIQUID PUSH PULL OPERATION 1 Connect the unit as shown in Diagram 2 Note The recovery tank must be...

Page 5: ...ure 1 Once loose remove the suction port filter cartridge as shown in Figure 2 Either clean the current cartridge or replace with new cartridge Inspect O ring Re lubricate with compressor oil or equivalent Place filter cartridge back into suction port fitting Hand tighten this assembly back onto the CR700 Use a 5 8 socket or boxed end wrench to tighten 1 8 of a turn Do not over tighten damage to t...

Reviews: