2. Take care not to contaminate the detector probe tip if the part

being tested is contaminated. If the part is particularly dirty or
condensate (moisture) is present, it should be wiped off with a
dry shop towel or blown off with shop air. No cleaners or sol-
vents should be used, since the detector may be sensitive to
their ingredients.   

3. Visually trace the entire refrigerant system and look for signs of

air conditioning lubricant leakage, damage, and corrosion on all
lines, hoses, and components.  Each questionable area should
be carefully checked with the detector probe, as well as all fit-
tings, hose to line couplings, refrigerant controls, service ports
with caps in place, brazed or welded areas, and areas around
attachment points and hold-down on lines and components.  

4. Always follow the refrigerant system around in a continuous

path so that no areas of potential leaks are missed. If a leak is
found, always continue to test the remainder of the system.  

5. At each area checked, the probe should be moved around the

location, at a rate no more than 25 to 50 mm/second (1-2
in/second), and no more than 5 mm (1/4 in) from the surface,
completely around the position. Slower and closer movement of
the probe greatly improves the likelihood of finding a leak.

6. An apparent leak shall be verified at least once by blowing shop

air into the area of the suspected leak, if necessary and repeat-
ing the check of the area. In cases of very large leaks, blowing
out the area with shop air often helps locate the exact position
of the leak.

7. Leak testing of the evaporator core while in the air conditioning

module shall be accomplished by turning the air conditioning
blower on high for a period of 15 seconds minimum, shutting it
off, then waiting for the refrigerant to accumulate in the case for
ten minutes. Next, insert the leak detector probe into the blow-
er resistor block or condensate drain hole if no water is present,
or into the closest opening in the heating/ventilation/air condi-
tioning case to the evaporator, such as the heater duct or a vent
duct. If the detector alarms, a leak apparently has been found.

8. Following any service to the refrigerant system, and any other

service which disturbs the refrigerant system, a leak test of the
repair and of the service ports of the refrigerant system should
be done.

OPERATING TIPS

Windy Conditions:

Do not attempt to find a leak in windy areas.

Even very large leaks may be impossible to find as the escap-
ing gas is quickly dissipated into the atmosphere. If necessary,
fabricate a gas trap using aluminum foil around joints or fittings
or otherwise shield the search area from the wind.   

Recommended Sensitivity Setting:

MAC recommends begin-

ning the leak test at level five or six. The best range of sensitiv-
ity is one that allows the variable output alarm and or visual indi-
cators to operate within the given 10 LED segments without full
saturation of the alarm. NOTE: The sensitivity range you have
selected is too high when the highest audible tone is continual-
ly achieved or all ten visual LEDs are constantly lit. Select a
lower sensitivity setting and try again.

Selective Filter Housing

: The presence of moisture in a leak

test area will cause corona leak detectors to false alarm. When
searching for leaks around evaporators or other areas where
high moisture content is present, housing with the patented
Selective Filter Housing. This filter will eliminate false alarms
caused by the presence of moisture.

4

Summary of Contents for LS780B

Page 1: ...CTOR DETECTOR DE FUGAS REFRIGERANTE DÈTECTEUR DE FUITE POUR RÉFRIGÉRANTS KÄLTEMITTEL LECKSUCHGERÄT LS790B OWNER S MANUAL MANUAL DE USUARIO MANUAL D UTILISATION BEDIENUNGSANLEITUNG U S PATENT 4 609 875 5 264 833AND 5 371 467 ...

Page 2: ...ENGLISH 2 6 ESPAÑOL 7 10 FRANÇAIS 11 14 DEUTSCH 15 19 ...

Page 3: ... and practical features pro vides the professional with the absolute feedback they need to confidently say the leak is here The following pages contain all of the necessary information you will need to properly operate maintain or leak test using the LS790B A C DETECTOR Please take the time to thoroughly read and understand the enclosed points prior to operating the unit If you have any questions ...

Page 4: ...as detected since the mode was selected or the CLEAR button was depressed Any concentration of gas less than the highest recorded concentration is locked out or ignored thereby eliminating the effects of background contam ination A distinct two tone alarm will sound when the probe is in the area of the highest refrigerant concentration This will be the leak source 5 CLEAR Key This key is used to a...

Page 5: ...ning the air conditioning blower on high for a period of 15 seconds minimum shutting it off then waiting for the refrigerant to accumulate in the case for ten minutes Next insert the leak detector probe into the blow er resistor block or condensate drain hole if no water is present or into the closest opening in the heating ventilation air condi tioning case to the evaporator such as the heater du...

Page 6: ...e when the two tone alarm only sounds at one specific area MAINTENANCE The LS790B A C DETECTOR is designed to require a minimal amount of field maintenance Regular cleaning of the sensor hous ing air vents replacement of the Ion Pump sensor and changing the batteries are the only maintenance needs Low Battery Condition If the center segment of the LED dis play located directly above the symbol ill...

Page 7: ...6 Figure 1 LSXSF SELECTIVE FILTER HOUSING ELIMINATES FALSE ALARM DUE TO THE PRESENCE OF MOISTURE LSXS ION PUMP SENSOR KEEP AIR VENTS OPEN AND CLEAN MAINTENANCE ...

Page 8: ...10gR por año Sensor de bomba iónica confiable de rápida respuesta Filtro selectivo elimina las falsas alarmas Mejoras en el circuito de sensibilidad energía y filtrado Indicadores de alarma audible y visual Detects All Halogenated Refrigerants Función LOCK OUT señala donde se encuentra la fuga principal LS790B Cumple con las especificaciones SAE J1627 REPUESTOS INCLUIDOS Su detector de escapes de ...

Page 9: ...Un segmento luminoso que se mueve de izquierda a derecha indica el nivel de sensibilidad seleccionado Cada posicion hacia la derecha representa una sensibilidad más alta Seleccione el grado de sensibilidad de acuerdo a la aplicacion Recomendamos empezar con un vivel bajo aumentándolo gradulamente si fuese necesario Recomendamos que se use la sensibilidad más alta que logre producir un cambio aprec...

Page 10: ...es de cualquier material que podiera bloquear la circulación de aire por el sen sor ION Pump Si los orificios se encuentran obstruidos apague el instrumento remueva la boquilla y separe los com ponentes La caja sensora de aluminio debe ser limpiada con un solvente ordinario y enjuagada con agua Deje que se seque completamente Inserte el sensor en la caja y ajustelo con la mano hasta que ofrezca re...

Page 11: ...10 LSXSF FILTRO ESTABILIZADOR DE HUMEDAD PARA ELIMINAR FALSAS ALARMAS LSXS SENSOR BOMB AIONICA MANTENGA LAS RANURAS DE VENTILACIóN DESTUPIDAS Figure 1 MANTENIMIENTO ...

Page 12: ...ible et visuelle Appuyer une 3ième fols retour à l alarme audible 3 Touche Sensibilité le LS790B offer 10 niveaux de sensibilité à sélectionner en relation au refrigerant en cause et la taille de la fuite L appareil chosit niveau 1 lors de mise en marche Appuyez et tenez la touche Sensibilité pour augmenter la sensi bité les LED changeront de gauche â droite minumum au maximum jusqu à la touche es...

Page 13: ...ionnés d après l application Le niveau de sensibilité le plus bas est automatiquement séle cionné lors de chaque mise en marche du Détecteur de Fuites Pour changer le niveau de sensibilité appuyez en continu sur la touche SENSITIVITY Le LED se déplacera de gauche á droite jusqu a ce que vous relâchiez la touche Chaque position plus à droite représente un niveau de sensibilité accru Sélectionnez le...

Page 14: ... qu aucune matiére ne le obstrue empêchant l air de circuler à travers le senseur de la Pompe à Ions Si les orifices se salis sent et s encrassent éteignez l instrument dévissez l embout et séparez en les éléments Le douilles à senseur en alumini um peuvent être nettoyées à l aide d un solvant doux et rincées ABONDAMMENT à l eau Laissez sécher complètement la douille et revissez MANUELLEMENT ce se...

Page 15: ...ENTRETIEN 14 LSXSF FILTRE D EVAPORATEUR élimine les fausses alarmes en présence d humidité LSXS Elément sensible Pompe à ions ION PUMP VEILLEZ A CE QUE LES ORIFICES SONT OUVERTES ET PROPES Figure 1 ...

Page 16: ...Freude an diesem technisch sehr hochwertigen Produkt haben Sollten Sie dennoch einige Fragen zu diesem Lecksuchgerät haben so scheuen Sie sich nicht uns anzurufen oder schicken Sie uns ein Telefax mit Ihren Fragen oder Anregungen Wir werden sehr schnell auf Ihre Fragen reagieren AUSTATTUNGEN Patentierter Mikroprozessor der das Schaltelement permanent kontrolliert Patentierter Ionen Pumpen Sensor z...

Page 17: ...r Ansaug u Ausblasdüsen achten Die Kontaktfläche von dem inneren Sensor mit einem weichen Lappen säubern Diese 4 Schritte empfehlen wir in regelmäßigen Abständen ca 1 x pro Woche ungeachtet der Verschmutzung zu wiederholen denn damit haben Sie eine gute Vorsorge getroffen Keine Reinigungs oder Lösungsmittel verwenden 3 Augenscheinliche Betrachtung des gesamten Kälte oder Klimaanlagen systems auf j...

Page 18: ...n den Leitungen wahrnehmen Ein unterschiedlicher 2 Ton Alarm wir für Sie hörbar wenn Sie nun mit dem Meßfühler an einer Stelle gelangen wo eine höhere Gaskonzentration ausfindig gemacht wird Dieser Punkt müßte dann die Leckage sein Anmerkung Seien Sie nicht irritiert Es ist möglich daß dieser 2 Ton Alarm auch neben dem soeben festgestellten Leck ertönt Dieses kann dann möglich sein wenn das Leck s...

Page 19: ...en Lappen abwischen Sollte das Sensorgehäuse hier speziell der Kopf von dem Gehäuse durch starke Feuchtigkeit oder andere ölige schmierige Einflüsse beeinträchtigt worden sein so sollten Sie unbedingt das komplette Sensorgehäuse gegen ein neues austauschen Somit sollten Sie auch immer ein patentiertes Sensorgehäuse mit Filter auf Lager haben Wir wünschen Ihnen viel Freude mit diesem neuen Lecksuch...

Page 20: ...ge This guarantee does not apply to instruments that have been altered misused or returned solely in need of field service maintenance All repaired instru ments will carry an independent 90 day warranty This repair poli cy does not include instruments that are determined to be beyond economical repair An instrument being returned to CPS for repair must be accompanied by an original bill of sale an...

Reviews: