D33351-RTL 120/520  Eng.

 

24.06.15 AM 

We reserve the right to make changes without notice

 D  X    H 1    X X X X 

1.0.0

24HR1

=flashes: select the program to be viewed and, if required, modify using 

 buttons

Before flashing ceases (about 5 seconds) press 

 twice more, rapidly, to access details of 

the program to be viewed or modified.

User has the following options:
– View and set or modify any parameter -------------------------------------------------

20.0.27  

– View e select timed programs  -------------------------------------------------------------

10.0.2  

– View times only  --------------------------------------------------------------------------------

10.0.3  

The page format differs depending on the program accessed: 

 P  r  o  G

2  4 H R 1    1 1 5 9 

 

25.  MENU NO. 1       

PROGRAM VIEWING AND SETTING (if permitted)

 

Permission

 Page n. 

Display 

Description                                                                           Memo

1.0.1

This menu allows simple viewing, setting or modifying of all timed and other programs. Viewing mode allows the settings of the 

programs to be checked only, but not modified.

View & Set allows them to also be modified as desired. The maximum number of 24-hour or 7-day programs may be established 

by the Site Manage via the MRL 608 C1 Master . 

TO VIEW, (and, if permitted, modify) THE PROGRAMS

.   PRESS 

   THE FOLLOWING PAGE APPEARS:

24 HOUR PROGRAMS

 X  X  X  c

XX.X°c 

= Desired temperature in the time period

D.X: 

= 24-hour program chosen to be viewed or modified

H.1: 

= First time period 

XX.XX: 

= Start time of period to be viewed or modified flashes

PRESS 

 TO SELECT THE PARAMETER TO BE VIEWED OR MODIFIED.

PRESS 

 TO MODIFY (IF PERMITTED)

Continue until all the starting times of the time periods and the 6 desired temperatures are set.

M O N  2 4 H r  X 

1.0.2

7-DAY PROGRAMS

 7  d    X

7d. X 

=  Indicates “7DAY X” in progress"

MON.: 

= Day of week

24Hr. X: 

= Program to associate with the day of the week 

PRESS 

   T

O SELECT  DAY OF WEEK TO WHICH TO ASSIGN THE PROGRAM

.

PRESS 

  TO CHOOSE THE 

PROGRAM TO ASSIGN.

The choice is between 

24H

our 1...7,  

 MAn

ual,   

Fro

sprot (

Heatp

)  

OFF

 

Continue until all 7 days of the week are completed.

The choice of the programs described above may be replaced by other types of programs imposed by different conditions.

These different conditions are linked to the three auxiliary switches E1, E2 and E3, and to one of the five settable annual programs.To 

each of these conditions, any chosen program may be associated (via Master or via PC). If more than one of these conditions is present, 

the priority order is: E1, E2, E3, ANNUAL.

Priority means that the first condition to appear in the list prevails.

The only condition present or the first  in order of priority, is indicated as follows:

– E1 = XXXX alternating with the associated program. XXXX is the name given to input E1; default: HELP (call)

– E2 = XXXX alternating with the associated program. XXXX is the name given to input E2; default: WIND (window open)

– E3 = XXXX alternating with the associated program. XXXX is the name given to input E3; default: ABSE (absent)

– ANNU. X = an annual period is running with an associated program. ANNU X alternates with the program.

It is possible to adjust the annual program setting locally  ------------------------------------------------------------------

10.0.4  

Local adjustment of the annual program is useful when the user wishes to use heating/conditioning even when the system 

is off as an annual program is in operation (e.g. HOLIDAY PERIOD). USER MUST REMEMBER TO RESET THE PREVIOUS 

PROGRAM WHEN LEAVING. This operation can be carried out using the same procedure used for choosing the programs  

(

Page number 0.0.1

)

WARNING: when a program is set using the auxiliary switches E1, E2 or E3, user may adjust the desired room temperature as 

if it were not a set program. 

PARTICULAR CASES OF PROGRAMS SET BY EXTERNAL FUNCTIONS

 

24.  MENU N. 0       FOR USER  

Permission

 Page n. 

Display 

Description 

 

Memo

Summary of Contents for RTL 120

Page 1: ...t input in POWER or TEMPERATURE On Off valve and fan coil ventilator switch with 0 10 Volt input Any other device that can be controlled via a three point relay and with 0 10 Volt input Internal or external room sensor Complete configuration of the limits and of the mode of use permitted to the user Three On Off inputs to be programmed as required Ample display with simplified readout for less exp...

Page 2: ...ups of local units names Each local unit can be assigned to a group so as to operate as a group instead of as a single unit To each group a name can be assigned Number of groups 0 9 Relay output Relay for selection heating conditioning 1 0 10 Volt output Maxiumum input load 1mA Min and Max limits settable via the Master Local alarm system All the alarm functions are available in order to have inst...

Page 3: ...cure the electronic unit to the built in base to avoid theft or tampering 7 Three module 503 enclosure for wall recessing 5 5 Exploded drawing of wall mounted RTL 520 2 3 1 4 5 6 7 1 Base for wall mounting 2 Terminal block for the electronic unit 3 Screw to secure the electronic unit to the built in base to avoid theft or tampering 4 Cover with rotary connection 5 Screw for securing cover to base ...

Page 4: ...if used E1 First AUXILIARY SERVICE switch or SEASON SWITCHING E2 Second AUXILIARY SERVICE switch E3 Third AUXILIARY SERVICE switch G Power supply 13 Volt P Cold pole of P Loc 0 Volt of the Y 0 10Volt output P Hot pole of the P Loc Y 0 10 Volt output 1 2 3 Control output relay switches The local unit REQUESTS heat HEAT or Cold COND 1 2 SWITCH CLOSED 2 3 SWITCH OPEN ThelocalunitDOESNOTREQUESTheat HE...

Page 5: ... Control of the output relay The output relay may be controlled in two modes PURE ON OFF the output relay is switched ON when the thermal unit must be switched on and vice versa PROPORTIONAL ON OFF the output relay is controlled cyclically with a programmable cycle duration This is a more sophisticated way of controlling the thermal unit in order to limit thermal excursions Factory setting the out...

Page 6: ...lished by the Master 18 TECHNICAL SETTINGS If permitted it is also possible locally to intervene locally with a series of checks and settings of technical parameters which are fully explained in the section devoted to screen displays It is also possible to program a local check for testing the electrical connections 19 LOCAL CLOCK The local unit has its own clock and calendar which are aligned as ...

Page 7: ...ETER CONTINES TO FLASH FOR A FEW SECONDS BEFORE RETURNING TO NORMAL CONDITIONS THE FLASHING PARAMETER IS CANCELLED BY PRESSING THE TWO PUSH BUTTONS TOGETHER As already described in both the Technical Data Sheet for the MRL 608 C1 Master and in this document the RTL 120 520 local unit may be configured in a number of different ways to adapt to the user s requirements Given the high number of possib...

Page 8: ...Essen tially the zone unit is converted into a thermostat with no time settings FROSP the frosp program with temperature as desired The frost protection tempera ture has a lower limit set in the Master on page 21 0 15 OFF always Off HEATP if control is in summer mode HEATP appears instead of FROSP PRESS TO CHOOSE DESIRED PROGRAM 0 0 1 no temperature seen NO TEMP SEEN 10 0 5 21 5 c actual room temp...

Page 9: ...HE PROGRAM PRESS TO CHOOSE THE PROGRAM TO ASSIGN The choice is between 24Hour 1 7 MAnual Frosprot Heatp OFF Continue until all 7 days of the week are completed The choice of the programs described above may be replaced by other types of programs imposed by different conditions These different conditions are linked to the three auxiliary switches E1 E2 and E3 and to one of the five settable annual ...

Page 10: ...ing summer operation instead of the FROSP function the HEATP function may be programmed 25 MENU No 1 PROGRAM VIEWING AND SETTING if permitted Permission Page n Display Description Memo P L I M X X d X X h 1 0 3 LIMITED TIME PROGRAM P LIM X X X X XXXX Program to assign for this function for limited time MAn Heap or FroP OFF 24 Hr 7d x P LIM Indicates that limited time program is in operation XXd Du...

Page 11: ... 26 1 MENU NO 2 chec READOUT OF TECHNICAL DATA Page n Display Description PRESS THE FOLLOWING PAGE APPEARS PRESS THE FOLLOWING PAGE APPEARS T A R Actual Room Temperature measured XX X c Value of measured room temperature t E S t T A R X X X c PRESS THE FOLLOWING PAGE APPEARS T A D Desired Room Temperature 21 0 c Value of Desired Room Temperature t E S t T A D 2 1 0 c PRESS THE FOLLOWING PAGE APPEA...

Page 12: ... t S W W TEST MENU COMPLETED PRESS TO RETURN TO THE START OF THIS MENU PRESS TO GO TO THE NEXT TECHNICAL MENU PRESS TO GO TO THE PREVIOUS TECHNICAL MENU t E S t 26 3 MENU NO 3 CONF LOCAL CONFIGURATION Page n Display Description PRESS THE FOLLOWING PAGE APPEARS ADD Telematic address of the Bus P Loc of the zone XXX Set desired address using push buttons PRESS THE FOLLOWING PAGE APPEARS GRUP The Gro...

Page 13: ...WARNING the logical status corresponds to the real position of the switch if it has been configured LIVE LOGICAL STATUS SWITCH CLOSED If on the other hand LIVE LOGICAL STATUS SWITCH OPEN the indication is reversed page 17 0 11 Master PRESS THE FOLLOWING PAGE APPEARS CORR tA Correction of room temperature measurement X X c value of the correction Room Temperature measurement may be corrected on thi...

Page 14: ...n switching is configured as LOCALE SETTING or INPUT E1 S E t S W W PRESS THE FOLLOWING PAGE APPEARS The internal clock of the zone unit may be adjsuted using this page This clock acts as an emergency backup of the centralised clock in the Master should a communication breakdown occur XXX Set the day of the week XX XX Set the time S E t X X X X X X X This menu provides information on how the zone ...

Page 15: ...in operation 00d Number of days for limited time max 7 days 05h Number of hours for limited time max 23 hours PRESS TO SELECT THE PARAMETER PREMERE or TO MODIFY THE PARAMETER MANUAL PROGRAM M A N 1 1 5 9 20 0 c Temperature for MANUAL mode MAN Indicates that MANUAL program is in operation 11 59 Current time PRESS TO SELECT THE PARAMETER PRESS or TO MODIFY THE PARAMETER FROSPROT OR HEATP PROGRAM CON...

Page 16: ...er to the RTB zone unit which are powered by 24 V and which receive C Bus from the Master itself The site is converted from COSTERZONE to MULTIZONE without changing the existing cabling as follows 24 Volt phase 24 Volt neutral C hot pole of C Bus which becomes P hot pole of P Loc 0C cold pole of C Bus which becomes P cold pole of P Loc BLACK BROWN BLACK RED G Power supply RTL P 0 V Power supply Bu...

Reviews: