Coster RTL 120 Manual Download Page 5

5

D33351-RTL 120/520  Eng.

 

24.06.15 AM 

We reserve the right to make changes without notice

9. COMMUNICATION BUS P-LOC & POWER SUPPLY

These matters are dealt with fully in technical specification regarding the Master of the “MULTIZONE”  MRL 608 

system. 

10. GENERAL FUNCTIONS

All the functions ofi RTL 120 and RTL 520 are exactly the same; the two devices differ only in regard to mechanical 

aspects and to the way they are installed.

11. TEMPERATURE CONTROL

The unit is essentially a room temperature controller which can function in several different ways, and with several 

different configurations, in order to best adapt to the ambient conditions it must control.

All the controller's main configuration parameters are set via the Master, which then sends them to the controller.

11.

1

 Basic control to create the Controller Output

The system comprises a basic algorithm for ambient control which is the same in each configuration.

This basic controller essentially calculates, without interruption, the CONTROLLER OUTPUT, i.e. the POWER (hot 

or cold), which the thermal unit (radiator, fan-coil or similar) has to deliver. 

The basic controller may function in the following modes:

– PROPOR INTEGRAL

– PROPORTIONAL ONLY 

– INTEGRAL ONLY

Choice of the correct option depends on the difficulties the controller may face in operating correctly.
The PROPOR INTEGRAL mode is usually the best suited.
The PROPORTIONAL BAND and/or Integral Time are parameters which require setting.
The factory (DEFAULT) settings are usually satisfactory.
These parameters are set independently for heating and conditioning control.

CONTROLLER OUTPUT (power required) results from the base controller's calculations.

CONTROLLER OUTPUT may be processed in various ways to adapt to the thermal unit.

The base controller is also provided with a neutral zone (adjustable from 0 to 3°C) as an acceptable room tempe-

rature tolerance range within which the thermal unit is not adjusted, in order to avoid too many interventions.

11.

2

 Control of the output relay

The output relay may be controlled in two modes: 

– PURE ON/OFF = the output relay is switched ON when the thermal unit must be switched on and vice versa.

– PROPORTIONAL ON/OFF= the output relay is controlled cyclically with a programmable cycle duration.

This is a more sophisticated way of controlling the thermal unit in order to limit thermal excursions.

Factory setting: the output relay is set to PURE ON/OFF (the simplest mode).

11.

3

 0...10 Volt output proportional to REQUIRED POWER (CONTROLLER).

This output is necessary when the thermal unit to control has a  0...10 Volt input to pilot power issued. 

For instance:

– FAN-COIL VENTILATOR SPEED CONTROL

– SMALL AIR-TREATMENT UNIT VENTILATOR SPEED CONTROL

– VARIABLE SPEED PUMP SPEED CONTROL 

– BOILER POWER OR TEMPERATURE CONTROL 

– ANY THERMAL UNIT WITH A 0...10 Volt INPUT

This output is proportional to the controller and therefore to the power required of the system at any specific time.

A minimum and maximum voltage limit may be set  for the output, for instance:

– to guarantee minimum ventilation even when no thermal power is required 

– to limit the top speed or power to avoid inconvenient noise or draughts.

11.

4

 Values of the CONTROLLER OUTPUT for ON/OFF of the relay controlled as PURE ON/OFF.

To better adapt to different circumstances, the threshold at which the output relay is switched ON and OFF may 

be set: 

– CONTROL VALUE to switch ON the relay = 90% of the power (factory  setting).

 

               – CONTRO VALUE to switch OFF the relay = 10% of the power (factory setting).

11.

5

 Cycle time for ON/OFF of relay controlled as ON/OFF PROPORTIONAL.

 

 

The cycle time is adjustable: default = 300 seconds.

11.

6

 Minimum ON and OFF times of output relay.

In whatever mode the output relay is controlled you can establish a minimum time for which it must remain ON and 

a minimum time for which it must remain OFF.    

 

             This function is very useful to avoid overworking the thermal unit when, for example, it is a  wall-mounted gas  

 

             boiler.

11.

7

 Heating and conditioning.

Control is provided for both heating or for conditioning the room.

This control order is received by the Master which has several modes for deciding on the basis of the type of 

installation and the use.  

Summary of Contents for RTL 120

Page 1: ...t input in POWER or TEMPERATURE On Off valve and fan coil ventilator switch with 0 10 Volt input Any other device that can be controlled via a three point relay and with 0 10 Volt input Internal or external room sensor Complete configuration of the limits and of the mode of use permitted to the user Three On Off inputs to be programmed as required Ample display with simplified readout for less exp...

Page 2: ...ups of local units names Each local unit can be assigned to a group so as to operate as a group instead of as a single unit To each group a name can be assigned Number of groups 0 9 Relay output Relay for selection heating conditioning 1 0 10 Volt output Maxiumum input load 1mA Min and Max limits settable via the Master Local alarm system All the alarm functions are available in order to have inst...

Page 3: ...cure the electronic unit to the built in base to avoid theft or tampering 7 Three module 503 enclosure for wall recessing 5 5 Exploded drawing of wall mounted RTL 520 2 3 1 4 5 6 7 1 Base for wall mounting 2 Terminal block for the electronic unit 3 Screw to secure the electronic unit to the built in base to avoid theft or tampering 4 Cover with rotary connection 5 Screw for securing cover to base ...

Page 4: ...if used E1 First AUXILIARY SERVICE switch or SEASON SWITCHING E2 Second AUXILIARY SERVICE switch E3 Third AUXILIARY SERVICE switch G Power supply 13 Volt P Cold pole of P Loc 0 Volt of the Y 0 10Volt output P Hot pole of the P Loc Y 0 10 Volt output 1 2 3 Control output relay switches The local unit REQUESTS heat HEAT or Cold COND 1 2 SWITCH CLOSED 2 3 SWITCH OPEN ThelocalunitDOESNOTREQUESTheat HE...

Page 5: ... Control of the output relay The output relay may be controlled in two modes PURE ON OFF the output relay is switched ON when the thermal unit must be switched on and vice versa PROPORTIONAL ON OFF the output relay is controlled cyclically with a programmable cycle duration This is a more sophisticated way of controlling the thermal unit in order to limit thermal excursions Factory setting the out...

Page 6: ...lished by the Master 18 TECHNICAL SETTINGS If permitted it is also possible locally to intervene locally with a series of checks and settings of technical parameters which are fully explained in the section devoted to screen displays It is also possible to program a local check for testing the electrical connections 19 LOCAL CLOCK The local unit has its own clock and calendar which are aligned as ...

Page 7: ...ETER CONTINES TO FLASH FOR A FEW SECONDS BEFORE RETURNING TO NORMAL CONDITIONS THE FLASHING PARAMETER IS CANCELLED BY PRESSING THE TWO PUSH BUTTONS TOGETHER As already described in both the Technical Data Sheet for the MRL 608 C1 Master and in this document the RTL 120 520 local unit may be configured in a number of different ways to adapt to the user s requirements Given the high number of possib...

Page 8: ...Essen tially the zone unit is converted into a thermostat with no time settings FROSP the frosp program with temperature as desired The frost protection tempera ture has a lower limit set in the Master on page 21 0 15 OFF always Off HEATP if control is in summer mode HEATP appears instead of FROSP PRESS TO CHOOSE DESIRED PROGRAM 0 0 1 no temperature seen NO TEMP SEEN 10 0 5 21 5 c actual room temp...

Page 9: ...HE PROGRAM PRESS TO CHOOSE THE PROGRAM TO ASSIGN The choice is between 24Hour 1 7 MAnual Frosprot Heatp OFF Continue until all 7 days of the week are completed The choice of the programs described above may be replaced by other types of programs imposed by different conditions These different conditions are linked to the three auxiliary switches E1 E2 and E3 and to one of the five settable annual ...

Page 10: ...ing summer operation instead of the FROSP function the HEATP function may be programmed 25 MENU No 1 PROGRAM VIEWING AND SETTING if permitted Permission Page n Display Description Memo P L I M X X d X X h 1 0 3 LIMITED TIME PROGRAM P LIM X X X X XXXX Program to assign for this function for limited time MAn Heap or FroP OFF 24 Hr 7d x P LIM Indicates that limited time program is in operation XXd Du...

Page 11: ... 26 1 MENU NO 2 chec READOUT OF TECHNICAL DATA Page n Display Description PRESS THE FOLLOWING PAGE APPEARS PRESS THE FOLLOWING PAGE APPEARS T A R Actual Room Temperature measured XX X c Value of measured room temperature t E S t T A R X X X c PRESS THE FOLLOWING PAGE APPEARS T A D Desired Room Temperature 21 0 c Value of Desired Room Temperature t E S t T A D 2 1 0 c PRESS THE FOLLOWING PAGE APPEA...

Page 12: ... t S W W TEST MENU COMPLETED PRESS TO RETURN TO THE START OF THIS MENU PRESS TO GO TO THE NEXT TECHNICAL MENU PRESS TO GO TO THE PREVIOUS TECHNICAL MENU t E S t 26 3 MENU NO 3 CONF LOCAL CONFIGURATION Page n Display Description PRESS THE FOLLOWING PAGE APPEARS ADD Telematic address of the Bus P Loc of the zone XXX Set desired address using push buttons PRESS THE FOLLOWING PAGE APPEARS GRUP The Gro...

Page 13: ...WARNING the logical status corresponds to the real position of the switch if it has been configured LIVE LOGICAL STATUS SWITCH CLOSED If on the other hand LIVE LOGICAL STATUS SWITCH OPEN the indication is reversed page 17 0 11 Master PRESS THE FOLLOWING PAGE APPEARS CORR tA Correction of room temperature measurement X X c value of the correction Room Temperature measurement may be corrected on thi...

Page 14: ...n switching is configured as LOCALE SETTING or INPUT E1 S E t S W W PRESS THE FOLLOWING PAGE APPEARS The internal clock of the zone unit may be adjsuted using this page This clock acts as an emergency backup of the centralised clock in the Master should a communication breakdown occur XXX Set the day of the week XX XX Set the time S E t X X X X X X X This menu provides information on how the zone ...

Page 15: ...in operation 00d Number of days for limited time max 7 days 05h Number of hours for limited time max 23 hours PRESS TO SELECT THE PARAMETER PREMERE or TO MODIFY THE PARAMETER MANUAL PROGRAM M A N 1 1 5 9 20 0 c Temperature for MANUAL mode MAN Indicates that MANUAL program is in operation 11 59 Current time PRESS TO SELECT THE PARAMETER PRESS or TO MODIFY THE PARAMETER FROSPROT OR HEATP PROGRAM CON...

Page 16: ...er to the RTB zone unit which are powered by 24 V and which receive C Bus from the Master itself The site is converted from COSTERZONE to MULTIZONE without changing the existing cabling as follows 24 Volt phase 24 Volt neutral C hot pole of C Bus which becomes P hot pole of P Loc 0C cold pole of C Bus which becomes P cold pole of P Loc BLACK BROWN BLACK RED G Power supply RTL P 0 V Power supply Bu...

Reviews: