26.5 MENU NO. 4 "TEST" = TESTING
Permission
Page n.
Display
Description
Memo
PRESS
THE FOLLOWING PAGE APPEARS:
IN.E1
= the logical status of the first auxiliary input (E1) is displayed.
OFF
= Logical status Off
ON
= Logical status On
WARNING: the logical status corresponds to the real position of the switch if it has been configured :
LOGICAL STATUS ON = SWITCH CLOSED. If, on the other hand:
LOGICAL STATUS ON = SWITCH OPEN the indication is reversed
(pag. 17.0.3 Master)
T E S T
I N E 1 O F F
PRESS
THE FOLLOWING PAGE APPEARS:
IN.E2
= The logical status of the first auxiliary input (E2) is displayed.
OFF
= Logical status Off
ON
= Logical status On
WARNING: the logical status corresponds to the real position of the switch if it has been configured :
LIVE LOGICAL STATUS = SWITCH CLOSED. If, on the other hand:
LIVE LOGICAL STATUS = SWITCH OPEN the indication is reversed
(page 17.0.7 Master)
T E S T
I N E 2 O F F
PRESS
THE FOLLOWING PAGE APPEARS:
T E S T
I N E 3 O F F
PRESS
THE FOLLOWING PAGE APPEARS:
O.1
= The zone unit's relay output can be controlled
NOTE: LEAVE AN INTERVAL OF AT LEAST 3 SECONDS BETWEEN
BUTTON
DEPRESSIONS
T E S T
O 1 O F F
4.0.1
4.0.2
IN.E3
= The logical status of first auxiliary input (E3) is displayed.
OFF
= Logical status Off
ON
= Logical status On
WARNING: the logical status corresponds to the real position of the switch if it has been configured:
LIVE LOGICAL STATUS = SWITCH CLOSED. If, on the other hand :
LIVE LOGICAL STATUS = SWITCH OPEN the indication is reversed
(page 17.0.11 Master)
PRESS
THE FOLLOWING PAGE APPEARS:
CORR.tA
= Correction of room temperature measurement
± X.X c
= value of the correction
Room Temperature measurement may be corrected on this page to align it with a
measurement made using external devices.
As the sensor incorporated in the zone unit has a tolerance of ± 0.3 °C, the correction is scar-
cely meaningful: the function has been allowed for psychological reasons, so that the user may
measure room temperature with a trusted device and set the unit accordingly.
This function is also of use when the installation site of the zone unit is open to thermal
disturbances, as it allows compensation.
C O n F
C O R R t A X X c
3.0.2
26.4 MENU NO. 4 "CONF" = READOUT OF TECHNICAL DATA
Page n.
Display
Description
"TEST" MENU COMPLETED:
PRESS
TO RETURN TO THE START OF THIS MENU
PRESS
TO GO TO THE NEXT TECHNICAL MENU
PRESS
TO GO TO THE PREVIOUS TECHNICAL MENU
PRESS
THE FOLLOWING PAGE APPEARS:
O 1 0 V o L t
= The 0...10 Volt output may be adjusted in 1-volt steps pushing buttons
NOTE: LEAVE AN INTERVAL OF AT LEAST 3 SECONDS BETWEEN
BUTTON
DEPRESSIONS
T E S T
O 1 0 V o L t X X
"TEST" MENU COMPLETED:
PRESS
TO RETURN TO THE START OF THIS MENU
PRESS
TO GO TO THE NEXT TECHNICAL MENU
PRES
TO GO TO THE PREVIOUS TECHNICAL MENU
PRESS
TO GO TO THE PREVIOUS TECHNICAL MENU