
51
ecotwin
COSMOGAS
Parameter
Permission
level
U.M.
Range
Factory setting
Costum
value
Mixing valve
(Enabling or disabling a mixing valve on heating circuit 1)
Installer
/
Selected -
Not selected
Not selected
Outdoor temp. 1 - CC (Don’t change) (**)
End user
°C
16...31
25
Outdoor temp. 2 - CC (Spring) (**)
End user
°C
26...37
32
Outdoor temp. 3 - CC (Summer) (**)
End user
°C
33...40
38
Water / outdoor temp. 1 - CC1 (Don’t change) (**)
End user
°C
18...40
23
Water / outdoor temp. 2 - CC1 (Spring) (**)
End user
°C
18...40
21
Water / outdoor temp. 3 - CC1 (Summer) (**)
End user
°C
18...40
18
Cooling curve 1 (CC1)
(Enabling or disabling the cooling outdoor reset)
End user
/
Selected -
Not selected
Not selected
(*)Setting parameters of the heating outdoor reset, refer to Figure 8-6.
(**)Setting parameters of the cooling outdoor reset, refer to Figure 8-7.
8 - USE