background image

+S

-S

CN1

or CN2

+V

-V

Load

C

1

OPEN

Fig. 3.2  When not using remote sensing function

Wire as close as possible

R1

+S

-S

CN1

or CN2

+V

-V

Load

C

1

R2

Fig. 3.3  When using remote sensing function

3.10 Signal Output (LED / Alarm)

¡

Functions of LED indicators and Output of Alarm are shown below. 
LED indicators and Output of Alarm are signals to check the pres-
ence/absence of voltage at the output terminal of a power supply 
and to detect fault conditions.

  The timing of signals might vary depending on input and load 

conditions.  Please evaluate thoroughly.

Table 3.2  LED indicator and Condition of Power supply

LED indicator

Condition of Power supply

Output

Blue

Orange

OFF

OFF

Turned off with remote ON/OFF, 

or decreased output voltage

OFF or 

Decreased

ON

OFF

Normal condition

ON

OFF

ON

Fault condition

OFF

Table 3.3  Explanation of alarm

Alarm

Output of Alarm

PG

The PG signals is “Low” when 

the power supply operates cor-

rectly. The signal turns to “High” 

when the power supply stops.

Open collector method

Good  : Low

 

 (0.5V max at 5mA)

Bad  : High

50V 5mA max

100k

W

0.1

m

F

PG

PGG

Fig.3.4  Internal circuit of PG

¡

Please note the followings when you use the alarms (PG signal).

 

1

  The PG signal turns to “High” when the output voltage is turned 

off with remote ON/OFF.

 

2

  When the output voltage drops to 40% or less of the rated out-

put voltage, the PG signal is “High”.

¡

Circuit of the alarm is isolated from input, output, FG, AUX and 
various function terminals.

3.11 Communication function

¡

The power supply provides an “Extended UART”(INFO terminal) 
digital interface that enables the user to configure many aspects 
of the device operation as well as monitor the input and output pa-
rameters.

  Please contact us for details.

¡

Extended UART is a communication protocol that enables single-
wire, bidirectional, insulated, and multiple communication of 
UART, which is a general-purpose communication standard.

  For details, please refer to the PCA Series Extended UART 

Manual.

¡

Communication function terminal is isolated from input, output, 
FG, AUX and various function terminals.

AC-DC Power Supplies Enclosed Type

Instruction Manual

PCA-12

Summary of Contents for PCA600F

Page 1: ...Inrush current protection circuit PCB Pattern Series Parallel operation availability Material Single sided Double sided Series operation Parallel operation PCA600F Active filter 15 400 7 3 250V 16A R...

Page 2: ...5 Assembling and Installation Method PCA 14 4 1 Series Operation PCA 13 4 2 Parallel Operation Master slave Operation PCA 13 5 1 Installation Method PCA 14 5 2 Derating PCA 15 5 3 Life expectancy and...

Page 3: ...G Each terminal of CN1 and CN2 are connected inside the power supply Table 1 2 Pin Configuration and Functions of CN3 Pin No Function Ground level 1 AUX Auxiliary output AUXG 2 AUXG Auxiliary output g...

Page 4: ...ient temperature 50 to 70 should be not more than the calculated value by linear interpolation Point A Fig 2 1 Temperature measurement point A thin electric wire could heat up and affect the power sup...

Page 5: ...al to logic to turn off output Note Please avoid applying a voltage exceeding the rated voltage to an output terminal Doing so may cause power supply to malfunction or fail If this is unavoidable for...

Page 6: ...pecifications of remote ON OFF Connection method Fig 3 1 a Fig 3 1 b Fig 3 1 c SW Logic Output ON SW open 0 1mA max SW open 0 1mA max SW close 0 5V max Output OFF SW close 3mA min SW close 3mA min SW...

Page 7: ...the power supply stops Open collector method Good Low 0 5V max at 5mA Bad High 50V 5mA max 100kW 0 1mF PG PGG Fig 3 4 Internal circuit of PG Please note the followings when you use the alarms PG sign...

Page 8: ...peration Wiring method with series operation is shown in Fig 4 2 The MS and SGND must be connected with each other Please use option part H PA 14 for connecting between MS and SGND Please decide one p...

Page 9: ...er 10 seconds or setting the voltage of RC2 terminal to logic to turn off output 5 Assembling and Installation Method 5 1 Installation Method To keep enough isolation between screws and internal compo...

Page 10: ...ectancy Mount Average ambient temperature yearly Life expectancy 0 Io 50 50 Io 100 All mounting direction Ta 35C 8 years 6 years Ta 40C 7 years 5 years Ta 50C 6 years 4 years Life expectancy R t 90 of...

Page 11: ...e a voltage a few times higher than the applied voltage When you test a unit for isolation between the input and output input and the terminal FG or between the output and the terminal FG short circui...

Page 12: ...0VAC When ambient temperature is 40 or less point B is 70 or less When ambient temperature is 70 point B is 75 or less The ambient temperature 40 to 70 should be not more than the calculated value by...

Reviews: