Fig.4.2 Connection method in parallel
*
Notes on parallel operation
(1) It is recommended to use the output current during parallel op-
eration at 10% or more of the total of the rated output current.
If a current exceeding the rated current is instantaneously taken
out where the total of the rated output currents is 10% or less,
the output may decrease or stop.
(2) Constant current set value external variable function cannot be
used.
(3) When the overcurrent condition occurs, the latch stop operation
is performed.
In order to release the latch stop operation, input is shut down
and input is restarted after 10 seconds or setting the voltage of
RC2 terminal to logic to turn off output.
5 Assembling and
Installation Method
5.1 Installation Method
¡
To keep enough isolation between screws and internal compo-
nents, the length of mounting screws should not exceed Fig. 5.1.
6mm max
1.5mm
Chassis of
PCA600F
Chassis of
customer system
Screw M4
Fig.5.1 Mounting screw
¡
Please do not block built-in fans and ventilation holes.
When the power supply is mounted by screws, please consider its
weight and set it in place. (Please see Fig. 5.2)
¡
If you use a power supply in a dusty environment, it can give a
cause for a failure. Please consider taking such countermeasures
as installing an air filter near the suction area of the system to pre-
vent a failure.
(a)
(c)
(b)
In case of (c), fix it
from both directions.
Fig.5.2 Installation method