Implement H-PA-14

Load

No.3 (Slave)

No.2 (Slave)

No.1 (Master)

Implement H-SN-53

Fig.4.2  Connection method in parallel

*

 Notes on parallel operation

(1)  It is recommended to use the output current during parallel op-

eration at 10% or more of the total of the rated output current.

     If a current exceeding the rated current is instantaneously taken 

out where the total of the rated output currents is 10% or less, 
the output may decrease or stop.

(2)  Constant current set value external variable function cannot be 

used.

(3)  When the overcurrent condition occurs, the latch stop operation 

is performed.

     In order to release the latch stop operation, input is shut down 

and input is restarted after 10 seconds or setting the voltage of 
RC2 terminal to logic to turn off output.

5 Assembling and 

Installation Method

5.1 Installation Method

¡

To keep enough isolation between screws and internal compo-
nents, the length of mounting screws should not exceed Fig. 5.1.

6mm max

1.5mm

Chassis of

PCA600F

Chassis of

customer system

Screw M4

Fig.5.1  Mounting screw

¡

Please do not block built-in fans and ventilation holes.

  When the power supply is mounted by screws, please consider its 

weight and set it in place. (Please see Fig. 5.2)

¡

If you use a power supply in a dusty environment, it can give a 
cause for a failure.  Please consider taking such countermeasures 
as installing an air filter near the suction area of the system to pre-
vent a failure.

(a)

(c)

(b)

In case of (c), fix it 

from both directions.

Fig.5.2  Installation method

AC-DC Power Supplies Enclosed Type

Instruction Manual

PCA-14

Summary of Contents for PCA600F

Page 1: ...Inrush current protection circuit PCB Pattern Series Parallel operation availability Material Single sided Double sided Series operation Parallel operation PCA600F Active filter 15 400 7 3 250V 16A R...

Page 2: ...5 Assembling and Installation Method PCA 14 4 1 Series Operation PCA 13 4 2 Parallel Operation Master slave Operation PCA 13 5 1 Installation Method PCA 14 5 2 Derating PCA 15 5 3 Life expectancy and...

Page 3: ...G Each terminal of CN1 and CN2 are connected inside the power supply Table 1 2 Pin Configuration and Functions of CN3 Pin No Function Ground level 1 AUX Auxiliary output AUXG 2 AUXG Auxiliary output g...

Page 4: ...ient temperature 50 to 70 should be not more than the calculated value by linear interpolation Point A Fig 2 1 Temperature measurement point A thin electric wire could heat up and affect the power sup...

Page 5: ...al to logic to turn off output Note Please avoid applying a voltage exceeding the rated voltage to an output terminal Doing so may cause power supply to malfunction or fail If this is unavoidable for...

Page 6: ...pecifications of remote ON OFF Connection method Fig 3 1 a Fig 3 1 b Fig 3 1 c SW Logic Output ON SW open 0 1mA max SW open 0 1mA max SW close 0 5V max Output OFF SW close 3mA min SW close 3mA min SW...

Page 7: ...the power supply stops Open collector method Good Low 0 5V max at 5mA Bad High 50V 5mA max 100kW 0 1mF PG PGG Fig 3 4 Internal circuit of PG Please note the followings when you use the alarms PG sign...

Page 8: ...peration Wiring method with series operation is shown in Fig 4 2 The MS and SGND must be connected with each other Please use option part H PA 14 for connecting between MS and SGND Please decide one p...

Page 9: ...er 10 seconds or setting the voltage of RC2 terminal to logic to turn off output 5 Assembling and Installation Method 5 1 Installation Method To keep enough isolation between screws and internal compo...

Page 10: ...ectancy Mount Average ambient temperature yearly Life expectancy 0 Io 50 50 Io 100 All mounting direction Ta 35C 8 years 6 years Ta 40C 7 years 5 years Ta 50C 6 years 4 years Life expectancy R t 90 of...

Page 11: ...e a voltage a few times higher than the applied voltage When you test a unit for isolation between the input and output input and the terminal FG or between the output and the terminal FG short circui...

Page 12: ...0VAC When ambient temperature is 40 or less point B is 70 or less When ambient temperature is 70 point B is 75 or less The ambient temperature 40 to 70 should be not more than the calculated value by...

Reviews: