DIGITAL SERVO DRIVE 

for BRUSHLESS/BRUSH MOTORS

COMMAnD InPUTS (COnTInUED)

HS (HIGH SPEED) DIGITAL InPUTS

These inputs have all the programmable functions of the GP inputs plus these additional functions on [In8] & [In9] 

which can be configured as single-ended or differential:

• PWM 50%, PWM & Direction for Velocity or Current modes
• Pulse/Direction, CU/CD, or A/B Quad encoder inputs for Position or Camming modes

DIFFEREnTIAL

SInGLE-EnDED

12 Vdc max

12 Vdc max

100 pF

1k

+5 V

C

10k

10k

10k

74HC14

[IN6]

[IN7-]

+5 V

100 pF

100 pF

100 pF

100 pF

10k

[IN9+]

[IN10+]

[IN8-]

1k

1k

1k

1k

10k

10k

33 nF

10k

74HC14

MAX3283

[IN11]
[IN12]

D

100 pF

1k

2.5V

+5 V

10k

100 pF

1k

+5 V

C

D

10k

[IN6]

74HC14

MAX3281

33 nF

10k

10k

10k

[IN11]
[IN12]

+

[IN7]
[IN8]

100 pF

1k

MAX3281

[IN9]

[IN10]

33nF

10k

10k

74HC14

[IN1]
[IN2]
[IN3]

A

+5.0 V

33nF

*3.3nF

10k

10k

*4.99k

74HC14

[IN4]

*[IN5]

+5.0 V

B

DIGITAL InPUTS

Xenus has twelve digital inputs, eleven of which have programmable functions. Input [In1] is dedicated to the drive Enable function. 

This is done to prevent accidental programming of the input in such a way that the controller could not shut it down.

Two types of RC filters are used: GP (general purpose) and HS (high speed). Input functions such as Pulse/Dir, CW/CCW, Quad A/B are 

wired to inputs having the HS filters, and inputs with the GP filters are used for general purpose logic functions, limit switches, and the 

motor temperature sensor. Programmable functions of the digital inputs include:

•  Positive Limit switch 

•  Step & Direction, or CU/CD 

 

•  Negative Limit switch 

  step motor position commands

 

•  Home switch 

•  Quad A/B master encoder 

 

•  Drive Reset 

  position commands

 

•  PWM current or velocity commands 

•  Motor over-temperature

 

•  CAN address bits 

•  Motion Profile Abort

DIGITAL InPUT CIRCUITS
24VDC MAX

24VDC MAX

Group

Inputs

A

1,2,3

B

4,5

C

6,7,8

D

9,10,11,12

PULL-UP/PULL-DOWn COnTROL

In addition to the active level and function 

for  each  programmable  input,  the  input 

resistors are programmable in four groups 

to  either  pull  up  to  +5  Vdc,  or  down  to 

ground.  Grounded  inputs  with  HI  active 

levels  interface  to  PLC’s  that  have  PnP 

outputs that source current from +24 Vdc 

sources. Inputs pulled up to +5 Vdc work 

with  open-collector,  or  nPn  drivers  that 

sink  current  to  ground.  The  table  below 

shows  the  PU/PD  groups  and  the  inputs 

they control.`

Summary of Contents for Xenus R10 Series

Page 1: ...pulse inputs reset digital torque or velocity reference or motor over temperature A twelfth input is dedicated to the drive Enable function Three programmable logic outputs are for reporting a drive...

Page 2: ...74HC14 Schmitt trigger 100 ns RC filter Vin LO 1 35 Vdc Vin HI 3 65 Vdc 12 Vdc max Inputs IN7 10 Single ended Comparator with 2 5 Vdc reference 100 ns RC filter Vin LO 2 3 Vdc Vin HI 2 45 Vdc Differen...

Page 3: ...motor cable shield feedback specifications GENERAL SPECIFICATIONS CONTINUED protections HV Overvoltage HV 400 Vdc Drive PWM outputs turn off until HV is less than overvoltage HV Undervoltage HV 60 Vd...

Page 4: ...le transformation ratio Resolution 14 bits equivalent to a 4096 line quadrature encoder Reference frequency 7 5 kHz Reference voltage 2 8 Vrms auto adjustable by the drive to maximize feedback Referen...

Page 5: ...1 DTE RxD 3 2 TxD 2 5 Gnd RxD TxD Gnd 5 3 RxD TxD 1 2 3 4 5 6 RJ 11 DTE RS 232 Xenus operates as a DTE device from a three wire full duplex RS 232 port at 9 600 to 115 200 Baud 8 bits no parity and on...

Page 6: ...drive with a higher CAN node address For more information on CANopen communications download the CANopen Manual from the Copley web site http www copleycontrols com motion downloads pdf CANopenProgram...

Page 7: ...e inputs or CANopen commands Green Slow Blinking Drive OK but NOT enabled Will run when enabled Green Fast Blinking Positive or Negative limit switch active Drive will only move in direction not inhib...

Page 8: ...position commands can be in either single ended or differential format Single ended signals should be sourced from devices with active pull up and pull down to take advantage of the high speed inputs...

Page 9: ...ed to the drive Enable function This is done to prevent accidental programming of the input in such a way that the controller could not shut it down Two types of RC filters are used GP general purpose...

Page 10: ...nal diode in the output is for driving PLC inputs that are opto isolated and connected to 24 Vdc The diode prevents conduction from 24 Vdc through the 1 k resistor to 5 Vdc in the drive This could tur...

Page 11: ...are less susceptible to noise that can degrade single ended outputs Encoder cables should use twisted pairs for each signal pair A A B B X X An overall shield should be used and for longer cables shie...

Page 12: ...ly This is useful in systems that use external controllers that also need the motor feedback encoder signals because these now come from J7 the Control connector In addition to eliminating Y cabling w...

Page 13: ...rame Ground 2 3 J2 U V W BRUSHLESS MOTOR Fuse Fuse 4 3 2 1 Mot U Mot V Mot W Frame Ground 3 L2 N 2 1 L1 L3 L2 L1 IN7 HS IN8 HS IN9 HS IN10 HS 10 IN1 Enable IN4 GP IN2 GP IN3 GP 3 Ref J7 10 Vdc Analog...

Page 14: ...H 1 4 5 J3 REGEN REGEN Frame Ground 2 3 J2 U V W BRUSHLESS MOTOR Fuse Fuse 4 3 2 1 Mot U Mot V Mot W Frame Ground 3 L2 N 2 1 L1 L3 L2 L1 IN7 HS IN8 HS IN9 HS IN10 HS 10 IN1 Enable IN4 GP IN2 GP IN3 G...

Page 15: ...3 J2 U V W BRUSHLESS MOTOR Fuse Fuse 4 3 2 1 Mot U Mot V Mot W Frame Ground 3 L2 N 2 1 L1 L3 L2 L1 11 IN7 HS 12 IN8 HS IN9 HS IN10 HS IN1 Enable IN4 GP IN2 GP IN3 GP 3 Ref J7 10 Vdc Analog Reference 1...

Page 16: ...smaller wire gauge these should not be used as part of a safety ground system Motor cases can be safety grounded either at the motor by earthing the frame or by a grounding conductor in the motor cab...

Page 17: ...e drive can radiate from the wire used for the safety ground connection In order to keep the path between the heatplate and earth as short as possible it s also recommended to mount the drive to the e...

Page 18: ...0 V recommended for XTL 230 36 R and XTL 230 40 R models AWG 14 600V for XTL 230 18 R Shielded cable required for CE compliance J2 Cable Connector Wago 51118008 or 721 104 026 047 RN01 0000 Euro style...

Page 19: ...OUT1 25 Multi Encoder A 8 IN11 GP 17 OUT2 26 Multi Encoder A 9 IN12 GP 18 OUT3 Pin Signal 6 No connect 5 TxD Output 4 Ground 3 Ground 2 RxD Input 1 No connect Pin Signal 1 CAN_H 2 CAN_L 3 CAN_GND 4 N...

Page 20: ...V recommended for XTL 230 36 R and XTL 230 40 R models AWG 14 600V for XTL 230 18 R Shielded cable required for CE compliance J2 Cable Connector Wago 51118008 or 721 104 026 047 RN01 0000 Euro style...

Page 21: ...Multi Encoder B 7 IN4 GP 16 OUT1 25 Multi Encoder A 8 IN11 GP 17 OUT2 26 Multi Encoder A 9 IN12 GP 18 OUT3 Notes 1 The total current drawn from the 5 Vdc outputs cannot exceed 400 mA Pin Signal 6 No c...

Page 22: ...recommended for XTL 230 36 R and XTL 230 40 R models AWG 14 600V for XTL 230 18 R Shielded cable required for CE compliance J2 Cable Connector Wago 51118008 or 721 104 026 047 RN01 0000 Euro style 5 0...

Page 23: ...P 15 Signal Gnd 24 Multi Encoder B 7 IN4 GP 16 OUT1 25 Multi Encoder A 8 IN11 GP 17 OUT2 26 Multi Encoder A 9 IN12 GP 18 OUT3 Notes 1 The total current drawn from the 5 Vdc output cannot exceed 400 mA...

Page 24: ...r and Temperature Sensor Xenus operates as a CAN node All commands are passed on the CAN bus CME 2 is used for setup and configuration before installation as CAN node Serial Cable Kit SER CK Connects...

Page 25: ...IVE for BRUSHLESS BRUSH MOTORS For multiple drive installations use the ordering guide on this page Computer equipment is the same as for single drive installations And Serial Cable Kit SER CK is used...

Page 26: ...tion controller card Using the minimum requirements will allow CME 2 to run but the performance will be significantly reduced Xenus takes digital position commands in Pulse Direction or CW CCW format...

Page 27: ...Line Filter Regen Resistor Optional Controller or PLC AC Mains 90 264 Vac 47 63 Hz 1 or 3 ph Copley Controls 20 Dan Road Canton MA 02021 USA Tel 781 828 8090 Fax 781 828 6547 Tech Support E mail sales...

Page 28: ...rews There are two protective sheets blue on one side and clear on the other Both must be removed when the interface pad is installed STEPS TO INSTALL 1 Remove the blue protective sheet from one side...

Page 29: ...heatsink and fan combinations enable operation at 55 C 1 2 3 3 M X M V M X M V M X M V Copley Controls 20 Dan Road Canton MA 02021 USA Tel 781 828 8090 Fax 781 828 6547 Tech Support E mail sales cople...

Page 30: ...ermal material 4 Heatsink hardware Regeneration Resistors Optional XTL RA 03 Regeneration resistor assembly for XTL 230 18 30 W XTL RA 04 Regeneration resistor assembly for XTL 230 36 XTL 230 40 model...

Reviews: