Fault description
Fault
Code
F5
Causes of possible failure
Temperature protection of
compressor top cover
•
Damage of compressor top cover switch
•
System blockage
F6
Fault with the Enviromental
temperature sensor on the
outdoor unit
•
Damage of the Enviromental temperature sensor on the outdoor unit
•
Poor contact of the Enviromental temperature sensor on the outdoor unit
•
Damage of wiring of the Enviromental temperature sensor on the
outdoor unit
•
Damage of the main PCB on the outdoor unit
F7
Fault with the over-voltage or
low voltage protection
•
Excessive in put voltage
•
Lower in put voltage
•
Damage of the driver PCB on the outdoor unit
•
Damage of the main PCB on the outdoor unit
•
Poor wiring
F8
Communication error
between the driver PCB and
main PCB of the outdoor unit
•
Chip damage
FA
F9
Fault with the suction
temperature sensor
Fault with the outdoor unit
EEPROM
•
Damage of the suction temperature sensor on the outdoor unit
•
Poor contact of the suction temperature sensor on the outdoor unit
•
Damage of wiring of the suction temperature sensor on the outdoor unit
•
Damage of the main PCB on the outdoor unit
H1
Fault with the drainage on N#
lndoor unit
•
Float switch disconnected or poor wiring
•
Error setting of model paramerers
•
Drain plug
•
Damage of the pump
H2
H3
Communication error between
the wired controler and main
PCB of the N# indoor unit
Fault of temperature sen sor
at N # evaporator inlet
•
Poor wiring
•
Damage of the wired controler
•
Damage of the main PCB on the indoor unit
•
Damage of temperature sensor at N # evaporator inlet
•
Poor conta et of temperature sensor at N # evaporator inlet
•
Damage of wiring of temperature sensor at N # evaporator inlet
•
Damage of the main PCB on the outdoor unit
H4
Fault of temperature sen sor
at N# evaporator outlet
•
Damage of temperature sensor at N# evaporator outlet
•
Poor conta et of temperature sensor at N# evaporator outlet
•
Damage of wiring of temperature sensor at N# evaporator outlet
•
Damage of the main PCB on the outdoor unit
H5
Protection lower temperature
discharge
•
Temperature sensor shedding
•
Damage of the main PCB on the outdoor unit
H6
H7
Low pressure switch
protection
•
Lack of the refrigerant
•
Stop valve unopened
•
Damage of low pressure switch
Low pressure protection
•
Lack of the refrigerant
•
Heat exchanger viscera