Conformity with standards

The safety switches fulfil the isolating
properties acc. to DIN EN 60947 as well as
the AC 23 motor switching capacity acc. to
DIN EN 60947.

The safety switches meet further
requirements such as those of the
DIN EN 60947-3, IEC 947-3 and the EC
directive on electromagnetic compatibility (89/
336/EEC) as well as of the EC directive on
electrical equipment for use within defined
voltage limits (73/23/EEC).

They have been designed, manufactured
and tested according to the state of the art
and to DIN ISO 9001.

Safety switches, industrial design KO

1

Technical Data

1.1

Technical details

Perm.ambient temperature:

-20° C up to +40° C  (standard version)

Deviating temperatures possible with special versions.

Perm.storage temperature in original packing:

-40° C to +80° C

Degree of protection. to EN 60529/IEC 529:

IP 65  (standard version)

Insulation class acc. to EN 60598 / IEC 598:

II  -  with metal flange

Test torques:
Cover screws

2.50 Nm

Cap nut of the plastic cable entry M12

1.65 Nm

Cap nut of the plastic cable entry M16 - M20

2.50 Nm

Cap nut of the plastic cable entry M25

3.50 Nm

Cap nut of the plastic cable entry M32 - M 63

5.00 Nm

Cap nut of the Ex-e metal cable entry M16

  7.5 Nm

e.g.  type E1WF/e (Ex-e)

Cap nut of the Ex-e metal cable entry M20

10.0 Nm

e.g. type E1WF/e (Ex-e)

Cap nut of the Ex-e metal cable entry M25

15.0 Nm

e.g. type E1WF/e (Ex-e)

Cap nut of the Ex-e metal cable entry M32

25.0 Nm

e.g. type E1WF/e (Ex-e)

Cap nut of the Ex-e metal cable entry M40

30.0 Nm

e.g. type E1WF/e (Ex-e)

Cap nut of the Ex-e metal cable entry M50

45.0 Nm

e.g. type E1WF/e (Ex-e)

Enclosure material  (catalogue version):

Sheet steel with powder coating

1.2

Safety switch  160 A Type Moeller, P7, 3 pole

Rated voltage:

400 V, 50/60 Hz

Rated current:

160 A

Perm. short circuit back-up fuse:

160 A gG/gL

Switching capacity AC 23:

160 A

1.2.2

Safety switch  250 A Type Moeller, P7, 3 pole

Rated voltage:

400 V, 50/60 Hz

Rated current:

250 A

Perm. short circuit back-up fuse:

250 A gG/gL

Switching capacity AC 23:

250 A

1.2.3

Safety switch  400 A Type Moeller, P10, 3 pole

Rated voltage:

400 V, 50/60 Hz

Rated current:

400 A

Perm. short circuit back-up fuse:

400 A gG/gL

Switching capacity AC 23:

400 A

1.2.4

Safety switch  630 A Type Moeller, P10, 3 pole

Rated voltage:

400 V, 50/60 Hz

Rated current:

630 A

Perm. short circuit back-up fuse:

800 A gG/gL

Switching capacity AC 23:

630 A

2

Safety instructions

The safety switches are not

suitable for hazardous areas.

For skilled electricians and

trained person in accordance with
national legislation, including the relevant
standards and, where applicable.

Modifications to the safety switch or
changes of its design are not permitted.

They shall be used for their intended
purpose and in perfect and clean
condition.
For replacement and repair, only genuine
Cooper Crouse-Hinds / CEAG spare parts
shall be used.

Repairs may only be carried out by
Cooper Crouse-Hinds / CEAG or a
qualified electrician in compliance with
the respective national regulations.

Prior to their taking into operation, the
safety switches shall be checked in
accordance with the instructions as per
section 6.

Before the initial operation, any foreign
matter will have to be removed from the
safety switch.
The safety switch cover can only be
removed in „On“ position.

Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions set in italics
the same as this text!

Summary of Contents for Crouse-Hinds CEAG KO

Page 1: ...ra lingua della Comunit à Europea potete richiederla al vostro rappresentante Cooper Crouse Hinds CEAG Montagevejledningen kan oversættes til andre EU sprog og rekvireres hos Deres Cooper Crouse Hinds CEAG leverandør Indien noodzakelijk kan de vertaling van deze gebruiksinstructie in een andere EU taal worden opgevraagd bij Uw Cooper Crouse Hinds CEAG vertegenwoordiging Tarvittaessa tämän käyttöoh...

Page 2: ... A 6p 7 1 2 6 Safety switch 315 A 6p 7 1 2 7 Safety switch 400 A 6p 7 1 2 8 Safety switch 630 A 6p 7 2 Safety instructions 6 3 Conformity with standards 6 4 Field of application 7 5 Application Properties 7 6 Installation 7 6 1 Mounting 7 6 2 Opening the device Electrical connection 7 6 3 Cable entry blanking plug 8 6 4 Flange plates 8 6 5 Closing the device cover closure 8 6 6 Taking into operati...

Page 3: ...12 1 65 Nm Druckschraube der KLE M16 M20 2 50 Nm Druckschraube der KLE M25 3 50 Nm Druckschraube der KLE M32 M 63 5 00 Nm Druckschraube der Metall Ex e KLE M16 7 5 Nm z B Typ E1WF e Ex e Druckschraube der Metall Ex e KLE M20 10 0 Nm z B Typ E1WF e Ex e Druckschraube der Metall Ex e KLE M25 15 0 Nm z B Typ E1WF e Ex e Druckschraube der Metall Ex e KLE M32 25 0 Nm z B Typ E1WF e Ex e Druckschraube d...

Page 4: ...en 6 2 Öffnen des Gerätes Elektrischer Anschluss Vor Öffnen der Geräte ist die Spannungs freiheit sicherzustellen bzw sind geignete Schutzmaßnahmen zu ergreifen Vor dem Öffnen ist der Schalter in EIN Stellung zu schalten Ein Schalten an der Achse des Schalter sockels bei geöffnetem Gehäuse ist nicht zulässig um den Schalter wieder korrekt schließen zu können Der elektrische Anschluss des Betriebs ...

Page 5: ...r Reparatur zurückzugeben Umbauten oder Änderungen am Betriebsmit tel sind nicht gestattet ausgenommen ist das Anbringen von zusätzlichen KLE im Rahmen der Zulassung des Betriebsmittels 9 Entsorgung Wiederverwertung Bei der Entsorgung des Betriebsmittels sind die jeweils geltenden nationalen Abfall beseitigungsvorschriften zu beachten Zur Erleichterung der Wiederverwertbarkeit von Einzelteilen sin...

Page 6: ...ogue version Sheet steel with powder coating 1 2 Safety switch 160 A Type Moeller P7 3 pole Rated voltage 400 V 50 60 Hz Rated current 160 A Perm short circuit back up fuse 160 A gG gL Switching capacity AC 23 160 A 1 2 2 Safety switch 250 A Type Moeller P7 3 pole Rated voltage 400 V 50 60 Hz Rated current 250 A Perm short circuit back up fuse 250 A gG gL Switching capacity AC 23 250 A 1 2 3 Safet...

Page 7: ... be locked in the OFF position by means of 3 padlocks see Fig 1 shackle diameter of the padlocks up to 4 6 mm A built in locking device prevents the opening of the enclosure in the OFF position The data according to sections 3 and 4 shall be taken into account during use Applications other than those described are not permissible without a written declaration of consent from Messrs Cooper Crouse H...

Page 8: ...he tests specified in the relevant national regulations are to be carried out Apart from that the correct functioning and installation of the apparatus in accordance with these operating instructions and other applicable regulations shall be checked The improper operation of safety switches may result in the invalidation of the guarantee 7 Maintenance Servicing The relevant national regulations wh...

Page 9: ...0 A 1 2 4 Interrupteur de sécurité 630 A Type Moeller P7 3 pôles Tension nominale 400 V 50 60 Hz Courant nominal 630 A Fusible de court circuit adm placé en amont 800 A gG gL Puissance de coupure AC 23 630 A 2 2 2 2 2 Consignes de sécurité Consignes de sécurité Consignes de sécurité Consignes de sécurité Consignes de sécurité Les interrupteurs de sécurité ne conviennent pas à l emploi en atmosphèr...

Page 10: ...e doit pas être endommagé Interrupteurs de sécurité type industriel KO 1 2 5 Interrupteur de sécurité 250 A Type ABB OETL 6 pôles Tension nominale 400 V 690 V 50 60 Hz Courant nominal 270 A Fusible de court circuit adm placé en amont 400 A 400 A gG gL Puissance de coupure AC 23 250 A 250 A 1 2 5 Interrupteur de sécurité 315 A Type ABB OETL 6 pôles Tension nominale 400 V 690 V 50 60 Hz Courant nomi...

Page 11: ... en service Mise en service Avant la mise en service de l appareil les vérifications spécifiées dans les règlements nationaux individuels devront être exécutées De plus il faudra vérifier son fonctionnement et installation corrects en conformité avec ce mode d emploi et avec d autres règlements y applicables L utilisation incorrecte de ces commutateurs peut annuler la garantie 7 Maintien Entretien...

Page 12: ...bH Cooper Crouse Hinds GmbH Cooper Crouse Hinds GmbH Cooper Crouse Hinds GmbH Neuer Weg Nord 49 D 69412 Eberbach Germany Phone 49 0 6271 806 500 Fax 49 0 6271 806 476 Internet www CEAG de E Mail Info ex ceag de GHG980700xP0001 D E F _ Auflage 0604 x ...

Reviews: