background image

88888

Cooper Crouse-Hinds GmbH

2

Safety instructions

2.1

Principls

The operations must be carried out

by electrical suitably trained in

hazardous area with knowledge

of increased safty explosion

protection IEC 60079-14.

Do not use this Ex-d enclosure in

hazardous area without complete

approval. The Ex-d enclosure are not

suitable for Zone 0 and Zone 20

hazardous areas.

The requirements of the EN 60079-31

regarding excessive dust deposits and

temperature to be considered from the

user.

After components have been installed,

Ex-d protective enclosures must be

inspected and fully certified by a testing

station or individuals authorized to

conduct such inspections and issue

certifications.

Observe the national safety rules and

regulations for prevention of

accidents as well as the safety

instructions included in these operating

instructions set in italics the same as this

text!

3

Conformity with standards

Conformity with standards

Conformity with standards

Conformity with standards

Conformity with standards

The Ex-d enclosure is conform to the
standards specified in the Attestation of
conformity.
It has been designed, manufactured and
tested according to the state of the art and to
DIN EN ISO 9001.

The Ex-d enclosure fulfil further requirements,
such as the EC directive on electromagnetic
compatibility (2004/108/EEC)

94/9 EC: Equipment and protective systems
intended for use in potentially explosive at-
mospheres.

4

Field of application

Ex-d enclosures that have been fully certified
by a testing station/authorized individual after
inspection are suited for use in Zone 1/2 and
Zone 21/22 hazardous areas (areas at risk of
explosion) as defined in IEC 60079-10-1 and
IEC 60079-10-2.

The enclosure materials used, including any
external metal parts, are high quality
materials that ensure a corrosion resistance
and resistance to chemical substances
according to the requirements for use in a
”normal industrial atmosphere”:

- aluminium alloy pressure casting

Optionally, a surface protection for tropical
and sea climates, etc. is also available for
use in extremely aggressive atmospheres.

5

Use / Properties

Ex-d enclosures that have been fully certified by
a testing station/authorized individual after
inspection are used, within the limitations of the
permissible power loss, to distribute electrical
energy, e.g. for lighting, heating and control
circuits, etc.
This may involve use of devices or components
that, during operation or in the event of a
malfunction, may produce sparks, arcing or hot
surfaces, e.g. switches, fuses, contactors,
relays, non-sparking electrical or mechanical
devices as well as control and display elements
with the appropriate, separately certified
elements, terminals or busbar systems.

Ex-d Enclosures may be ordered with an
optional seal in the enclosure cover
(see Fig. 1). With the appropriate controls and
cable entries, the enclosures may be used in
areas requiring the IP66 protection class in
accordance with EN/IEC 60529.

Certified elements may be installed in the
enclosure cover.
Certified Ex-d elements and/or certified cable
feeds/cable entries or busbar boxes with Ex-e
protection type may be installed in the side walls.

Cables and wires may be inserted either directly
through approved Ex-d-rated cable feeds and
cable entries, certified conduits or through flange-
mounted connection boxes.

The data according to sections 3 and 4

shall be taken into account during use.

During operation the instructions stated

in section 7 of the operating instructions

shall be observed.

CCH assumes no liability for damage arising
from improper use.

Operating instructions

Explosion-protected Ex-d enclosures GHG 64

Fig. 1

Optional cover seal

Summary of Contents for CEAG GHG 64

Page 1: ...XNFLMX YDOVWV YDORG YDUDW SLHSUDV W MXVX YDOVWV DWELOG JDM RRSHU URXVH LQGV S UVW YQLHF E 0 LVWJ X MLWROEX GDQ LO PDQZDO ILO OLQJZD QD MRQDOL WDJ KRP PLQJ DQG LU UDSSUH HQWDQW WD RRSHU URXVH LQGV I SD...

Page 2: ...lverschluss 5 6 4 Inbetriebnahme 6 7 Instandhaltung Wartung 6 8 Reparatur Instandsetzung 6 9 Entsorgung Wieder verwertung 6 10 Technischer Anhang 10 1 Anhang Typenschl ssel 11 Contents Contents 2 1 Te...

Page 3: ...60 C f r Kategorie IIB g ltig f r alle Gr en 55 C bis 55 C bei Einsatz in Zone 21 22 Zul Lagertemperatur in Originalverpackung 50 C bis 80 C Schutzart nach EN IEC 60529 IP65 IP66 mit Dichtung im Geh u...

Page 4: ...geh use aus Leichtmetall GHG 64 Fig 1 Geh useoberteil mit optionaler Dichtung Bei einem Einsatz in extrem aggressiver Atmosph re k nnen Sie zus tzliche Informa tionen ber die Chemikalienbest ndigkeit...

Page 5: ...betrachtet Unsachgem e Installation der Ger te f hrt zum Verlust der Garantie 6 3 Schlie en des Ger tes Deckelverschluss Alle Fremdk rper aus dem Ger t Alle Fremdk rper aus dem Ger t Alle Fremdk rper...

Page 6: ...m ssen glatt und unverkratzt sein Anschlie end die Spaltfl chen wieder gleichm ig mit Fett bestreichen Fetttyp Renocal Unitemp 2 50 C bis 100 C FN 745 94 DIN VW TL 745 Sch den an Teilen der druckfeste...

Page 7: ...C for Zone 21 22 Other temperatures possible with special versions Perm ambient temperature in original packing 50 C to 80 C Degree of protection to EN IEC 60529 IP54 IP66 with seal Insulation class t...

Page 8: ...uding any external metal parts are high quality materials that ensure a corrosion resistance and resistance to chemical substances according to the requirements for use in a normal industrial atmosphe...

Page 9: ...closures with or without switches it is necessary to ensure that there is no voltage or to take suitable protective measures The connection of explosion protected Ex d enclosures and distributions may...

Page 10: ...operator according to the respective operating conditions Special attention should be given to ensuring Integrity and tightness of the enclosure Integrity of the flameproof joints on the enclosure bod...

Page 11: ...H2 Leergeh use empty enclosure Gr e H he x Breite x Tiefe in mm Size high width depth 01 210 x 210 x 191 02 210 x 320 x 191 03 210 x 320 x 284 04 320 x 320 x 191 05 320 x 320 x 284 06 320 x 430 x 191...

Page 12: ...use Hinds GmbH Neuer Weg Nord 49 D 69412 Eberbach Germany Fone 49 0 6271 806 500 Fax 49 0 6271 806 476 Internet www ceag de E Mail sales cch de cooperindustries com GHG 640 7003 P0001 D E F b Auflage...

Reviews: