WIRING DIAGRAMS: 

Supervised System 

                

 

 

Isolated inputs are provided for independent supervision and actuation of the three audible inputs. 

 

Unsupervised System 

Common Positive 

Unsupervised System 

Common Negative 

 

 

 

For  applications  not  requiring  supervision:  connect  all  positive  (+)  terminals  to 
the  power  source.    The  negative  (-)  terminal  for  each  appliance  will  actuate  the 
appliance. 

 

For  applications  not  requiring  supervision:  connect  all  negative  (-)  terminals  to 
the  power  source.    The  positive  (+)  terminal  for  each  appliance  will  actuate  the 
appliance. 

 

In case of simultaneous inputs, the three audible outputs are self-prioritized as follows:  1st  priortiy= PRI 1; 2nd priority = PRI 2; 3rd priority = PRI 3.  Leave 
any unused inputs disconnected. 

 

 

 

1. 

AMT Multitone appliance models have in-out wiring terminals that accept two #12 to 
#18 American Wire Gauge (AWG) wires at each screw terminal.  Strip leads 3/8 inches 
and connect to screw terminals. 

2. 

Break  all  in-out  wire  runs  on  supervised  circuits  to  assure  integrity  of  circuit 
supervision  as  shown  on  left.    The  polarity  shown  in  the  wiring  diagrams  is  for 
operation of the appliances.  The polarity is reversed by the FACP during supervision. 

 
MOUNTING OPTIONS: 

 

CAUTION:  

The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting  option.  If 

these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. 
 
Although  the  limits  shown  for  each  mounting  option  comply  with  the  National  Electrical  Code  (NEC),  Cooper  Notification  recommends  use  of  the  largest 
backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum 
stress on the product from wiring. 
 

FLUSH (4" BOX)

A

10

4

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

 SCREW COVERS

#8-32 SCREWS

4" SQ. X 2-1/8"

DEEP BACKBOX

B

FLUSH (2-GANG BOX)

2-GANG x 2-1/2"

DEEP BACKBOX

AWG #18  AWG #16  AWG #14  AWG #12

10

8

8

4

MAXIMUM NUMBER OF CONDUCTORS

#6-32 SCREWS

SCREW COVERS

C

SURFACE (INDOOR/OUTDOOR)

#8-18 SCREWS

INDOOR/OUTDOOR

WOOD

 SCREWS

SCREW COVERS

12

12

12

12

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

BACKBOX IOB

D

CONCEALED CONDUIT MOUNTING

EXISTING

BOX 

#8-18 SCREWS

INDOOR/OUTDOOR

SCREW COVERS

12

12

12

12

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

BACKBOX IOB

 

 