background image

P83611 J 

Sheet 2 of 4

 

When calculating the total currents:  Use Table 2 to determine the highest value of “RMS Current” for an individual AMT (across the expected operating voltage 
range of the AMT’s), then multiply these values by the total number of AMT’s; be sure to add the currents for any other appliances powered by the same source 
and include any required safety factors. 

 

If the peak current exceeds the power supplies’ peak capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the 
appliances connected to the supply and the voltage may not recover in some types of power supplies.  For example, an auxiliary power supply that lacks filtering 
at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic. 

 

The AMT Multitone audible appliances produce a brief inrush current that lasts for just 2 microseconds but can reach a peak value of 8.0 Amps (11.2 amps for 
FWR input). 

 
AMT MULTITONE SETTINGS:  

 

The Jumper Plug (DP1) and Switch (SW1) of the AMT Multitone Appliances, shown in Figure 1, are used to set the input voltage dBA sound output level and 
alarm tone.  The factory settings are shown below.  

Read these instructions carefully before changing any of these factory settings. 

 

Figure 1: 

 

PC Board Layout Showing Location 

of Jumper Plug (DP1) and Switch (SW1) 

 

+PRI 1-

+PRI 2-

+PRI 3-

24

12

24

12

 

 

The Factory Settings are: 
 
24VDC:   

DP1 SET ON 24 

HIGH dBA:  SW1  POS 1 = 1 

Priority 1 (PRI 1)   HORN TONE:

Priority 2 (PRI 2)   BELL TONE:  

Priority 3 (PRI 3)   SIREN TONE: 

SW1  POS  2, 3, 4 = 1, 1, 1

 

 

NOTES: 

1.

 

Set desired input voltage and dBA sound output level as follows (Refer to Figures 2 and 3). 

2.

 

AMT Multitone Appliances are field set for input voltage and dBA sound output level by inserting a Jumper Plug (DP1) and adjusting a four position Switch 
(SW1) as shown in Table 3 and Figures 2 and 3.  Use DP1 to select the desired voltage and SW1 Position 1 to select the dBA sound output level. 

 

Table 3:  Input Voltage and dBA Sound Output Level Settings 

Input Voltage and Decibel Level 

DP1 and SW1 Settings 

 

 

24 

VDC

/HIGH   

dBA: 

Set DP1 on 24;  set SW1  POS 1 on 1 (Factory Setting) 

 

 

24 

VDC

/

STD

 

 

dBA: 

Set DP1 on 24;  set SW1  POS 1 on 0 

 

 

12 

VDC

/HIGH   

dBA: 

Set DP1 on 12;  set SW1  POS 1 on 1 

 

 

12 

VDC

/

STD

 

 

dBA: 

Set DP1 on 24;  set SW1  POS 1 on 1 

 

Figure 2: 

 

Figure 3: 

Jumper Plug (DP1) Settings 

 

 

 

(Use Needle Nose Pliers to Lift and Properly Insert the Jumper Plug) 

 

Switch (SW1) Settings 

 

 

 

WARNING:    DO  NOT  APPLY  24VDC  INPUT  IF  THE  JUMPER  PLUG (DP1)  IS  SET  ON  12.    THIS  CAN  DAMAGE  THE  UNIT.   DOUBLE 

CHECK THE JUMPER PLUG (DP1) AND SWITCH (SW1) SETTINGS TO MAKE SURE THEY ARE CORRECT.  IMPROPER SETTINGS CAN 
DAMAGE  THE  UNIT  OR  RESULT  IN  NO SOUND  OUTPUT  OR  A  dBA  SOUND  OUTPUT  LEVEL  THAT  IS  BELOW THE MINIMUM CODE 
REQUIREMENTS  FOR  PUBLIC  MODE  FIRE  PROTECTION,  WHICH  COULD  RESULT  IN  PROPERTY  DAMAGE  AND  SERIOUS  INJURY 
OR DEATH TO YOU AND/OR OTHERS. 

 

NOTES:

   

1.

 

The prioritized tones contained in each group is factory pre-set which can not be changed. 

2.

 

The  Code  3  Horn  and  Code  3  Tone  (set  on  HIGH  dBA)  incorporate  the  temporal  pattern  specified  by  ANSI/NFPA  for  standard  emergency  evacuation 
signaling.  They should be used only for fire evacuation signaling and not for any other purpose. 

 

The Bell Tone can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate independently.  All other 
tones are recommended for use only on continuous (non-coded) systems. 

Reviews: